  2000 Insert Installation and Operation Manual 
 
application is verified and authorized by a qualified installer. Otherwise, the diameter of the flue 
should be 6 inches. The reduction of liner diameter to less than 6" should only be done if the total 
height of the masonry chimney is greater than 20 feet. 
 
9.4 LINER INSTALLATION 
We recommend the use of a chimney liner (rigid or flexible) to ensure satisfactory performance.  
To  ensure  an  optimal  draft,  we  also  strongly  recommend  adding  a  minimum  of  12"  rigid  liner 
between the top of the masonry chimney and the rain cap.  In all cases, liners should be installed 
in  accordance  with  the  liner  manufacturer's  instructions,  including  instructions  for  extension 
above the masonry. 
Use Listed Chimney Liners – UL 1777, CAN/ULC S635. 
In order to connect the insert to the liner, refer to Section 9.5 Chimney liner installation.  
ATTENTION  INSTALLER:    When  positioning  the 
unit  in  a  fireplace  opening  prior  to  the  flue 
installation,  install  the  insert  into  the  opening 
until  the  top  lip  of  air  jacket  is  flush  with 
fireplace facing. 
If lag‐bolts or anchors are to be used to secure 
the insert, the hole locations should be marked 
with  the  unit  in  place.    Remove  the  insert  and 
locate the anchors. 
 
  _ _____________________________________________________________________________  4 1 