  2000 Insert Installation and Operation Manual 
8.4 POSITIONING THE UNIT 
It  is  necessary  to  have  a  floor  protection  made  of  non‐combustible  materials  that  meets  the 
measurements specified in table FLOOR PROTECTION (see Section 8.5. To determine the need to 
add floor protection (D) beyond the hearth extension, you must do the following calculation using 
the data in Table Data for floor protection calculation of this section: D = B ‐ (A ‐ C). If the value 
(D) is negative or zero, you do not have to add more floor protection in front of the unit, because 
the masonry fireplace hearth extension is large enough. If the value (D) is positive, you will need 
floor protection in front of the hearth extension at least equivalent to the result (D). 
Here  is  a  sample  calculation  to  determine  the  need  to  add  a  non‐combustible  materials  floor 
protection. For someone living in the USA whose insert would protrude 3" (76 mm) into the room 
(C) the calculation would be: 
 
Value D = B ‐ (A ‐ C) 
 
Value D = 16" ‐ (16" ‐ 3") 
 
Value D = 16" ‐ 13" 
 
Value D = 3" 
Non‐combustible floor protection of at least 3" (76 mm) in depth must be installed in front of the 
fireplace hearth extension.  
 