PART B ‐ INSTALLATION 
6 PRE‐INSTALLATION MASONRY FIREPLACE REQUIREMENTS 
 
The masonry fireplace must meet the minimum requirements found in the building code enforced 
locally,  or  the  equivalent  for  a  safe  installation.  Contact  your  local  Building  Inspector  for 
requirements in your area.  An inspection of the fireplace should include the following: 
1. CONDITION OF THE FIREPLACE AND CHIMNEY: 
The masonry fireplace and chimney should be inspected prior to installation, to determine that 
they  are  free  from  cracks,  loose  mortar,  creosote  deposits,  blockage,  or  other  signs  of 
deterioration.    If  evidence  of  deterioration  is  noted,  the  fireplace  or  chimney  should  be 
upgraded and/or cleaned prior to installation. 
Masonry  or  steel,  including  the  damper  plate,  may  be  removed  from  the  smoke  shelf  and 
adjacent damper frame if necessary to accommodate the insert's chimney liner, provided that 
their removal will not weaken the structure of the fireplace and chimney, and will not reduce 
protection for combustible materials to less than that required by the building code. 
2. INSTALLATION INTO AN EXISTING FACTORY‐BUILT ZERO‐CLEARANCE FIREPLACE: 
It  is  possible  to  install  a  wood  insert  into  an  existing  factory‐built  zero‐clearance  fireplace.  
However, there currently exists no UL or ULC standard specific to that type of installation.  The 
factory‐built  zero clearance  fireplace  must  be  listed;  that  is,  safety  certified  by  an accredited 
certification agency such as UL/ULC, Omni or Intertek).  It must be suitable for use with solid 
fuel and nothing in the owner's manual must specifically prohibit the installation of a fireplace 
insert.  When  in  doubt,  check  with  the  fireplace  manufacturer.    The  installation  of  the  zero‐
clearance fireplace MUST be thoroughly inspected by a qualified person to ensure that it still 
meets  the  manufacturer's  specifications.  The  chimney  must  be  at  least  1"  (25  mm)  larger  in 
diameter than the stainless steel liner that will run from the insert flue collar to the top of the 
chimney termination. 
Never  remove  parts  intended  to  insulate  the  zero‐clearance  fireplace  from  combustible 
material. Only readily detachable parts that are easily replaced, such as damper parts, screens, 
and doors, are to be removed from the fireplace.  These parts should be stored and available 
for reinstallation if the insert is ever removed.  Removal of any parts which render the fireplace 
unfit for use with solid fuel requires the fireplace to be permanently labeled by the installer as 
being no longer suitable for solid fuel until the removed parts are replaced and the fireplace is 
restored to its original certified condition. Also, any air vents, grilles, or louvers that allow air 
circulation around the fireplace must not be removed or blocked. 