Setting The Carrier Address Id - Avaya G650 Installing

Avaya media gateway
Hide thumbs Also See for G650:
Table of Contents

Advertisement

For adequate ventilation and to conform with EIA-310D data rack standards, you need to provide the
following clearance:
12 inches (30 centimeters) in the rear
18 inches (45 centimeters) in the front
3 inches (7.6 centimeters) on the sides
!
Be sure the customer-supplied 19-inch (48-centimeter), EIA-310D standard, open rack is properly
installed, solidly secured to the floor, and grounded. If the rack is not secured to the floor, do not
proceed with the installation. Avaya does not recommended that you use enclosed data cabinets,
because they might not allow sufficient ventilation to the G650 Media Gateway.
!
It is very important to align the G650 Media Gateway with the correct holes in the frame because
the distance between each is not uniform. Use the G650/G600 Mounting Template, shipped with
each carrier, to help you align the holes.
Each G650 Media Gateway is 8U high. A typical data rack is 42U high. When you create a five-carrier
G650 Media Gateway stack, all but 3.5 inches (8.9 centimeters) of a typical rack is used. Mount the A
carrier low in the rack.
In a multiple G650 Media Gateway configuration, put the G650s in the rack with no vertical space
between them. If the G650 Media Gateways are not mounted adjacent with their fronts in the same
vertical plane, the TDM/LAN cable(s) cannot connect them.

Setting the carrier address ID

Set the carrier address ID either before or after installing each G650 Media Gateway. You set the carrier
address by inserting the address paddleboard in one of five connector slots on the upper right side of the
backplane. The slots are clearly marked as A, B, C, D, and E. All carriers ship with the address
paddleboard in connector slot A. If you are working on a B, C, D, or E carrier, you need to remove the
address paddleboard, and move it to the correct slot for a B, C, D, or E carrier.
To set the carrier address ID:
1
Loosen the thumb screws on the fan assembly and pull it straight out as shown in
Removing the fan assembly,
the assembly on top of the cabinet or hang it from the rear connector panel using the screws on the
back of the assembly. Leave the fan assembly off until the unit is completely installed in the rack.
2
Verify and, if necessary, set the carrier address ID for each G650 Media Gateway as shown in
Figure 5, Setting the G650 Media Gateway carrier address ID,
paddleboard in the connector slot that you want, A, B, C, D, or E.
Installing the Avaya G650 Media Gateway
June 2004
WARNING:
WARNING:
on page 36. You do not need to unplug the connection. You can place
Figure 4,
on page 36. Place the address
35