Grounding To An Ac Load Center More Than 50 Feet (15.2 Meters) From Media Gateway - Avaya G650 Installing

Avaya media gateway
Hide thumbs Also See for G650:
Table of Contents

Advertisement

Figure 36: Typical media gateway ground location
Figure notes
1
Media Gateway
2
Media Gateway Frame Ground
Terminal Block
3
6 AWG (#40) (16 mm
Ground Conductor
Grounding to an AC load center more than 50 feet (15.2 meters)
from media gateway
To ground to an AC load center more than 50 feet from the media gateway:
1
Mount the single-point ground block to any surface between the media gateways and the AC load
center single-point ground. The single-point ground block must be mounted to a non-metallic
surface.
2
At the bottom rear of the first media gateway, connect a 6 AWG (#40) (16 mm
GROUND wire to the media gateway frame ground terminal block. See
gateway ground location,
3
Route the opposite end of the wire to the single-point ground block and connect.
4
At the next (if provided) DC Power media gateway, connect a 6 AWG (#40) (16 4 mm
gateway GROUND wire to the media gateway frame ground terminal block GROUND
DISCHARGE bar.
86
6
4
5
1
2
widmgrn2 KLC 091603
4
5
6
2
) Supplementary
on page 63.
Installing the Avaya G650 Media Gateway
3
AC Load Center
Less than 50 Wire feet (15.2 m)
Approved Ground
Figure 17, Typical media
2
) media gateway
2
) media
June 2004