Either of these power sources can supply 50 Hz power to the AC load:
Non-US 5-wire, Y, 220/380 VAC. This source has 3 hot wires, 1 neutral wire, and 1 ground wire.
Non-US Delta, 4-wire, 220 or 240 VAC. This source has 3 hot wires and 1 ground wire.
Table 8: AC power sources and plug type
Power distribution unit
AC power distribution
(J58890CH) media gateway

Connecting small battery holdover

Grounding to an AC-powered media gateway (J58890CH)
AC-powered media gateway. Basically, the media gateways connect to the single-point ground terminal
block located at either the AC load center or to a separate single-point ground block wired to the AC load
center (or optional AC protector cabinet).
The approved ground wire must be a green (or green with yellow stripe), 6 AWG (#40) (16 mm
copper, stranded wire.
Bond all approved grounds at the single-point ground to form a single grounding electrode
system.
Grounding to an AC load center 50 feet (15.2 meters) or less
from media gateway
To ground an AC load center 50 feet or less from the media gateway:
1
At the bottom rear of the first media gateway, connect a 6 AWG (#40) (16 mm
GROUND wire to the media gateway frame ground terminal block. See
gateway ground location,
64.
2
Route the media gateway GROUND wire to the single-point ground block at the AC load center
and connect.
3
At the bottom rear of the next media gateway (if provided), connect a 6 AWG (#40) (16 mm
media gateway GROUND wire to the media gateway frame ground terminal block.
4
Route the media gateway GROUND wire to the single-point ground block at the AC load center
and connect.
62
Power sources
Single-phase 176-264
VAC
on page 63 and
NOTE:
If the media gateway is located remotely (in a separate room or building), connect the
media gateway GROUND wire to an approved ground.
Power input
200-240 Volts, 50-60 Hz
NEMA L6-30R. Installations
outside the United States require
a receptacle suitable for use in
the country of installation.