RealPresence Collaboration Server (RMX) 1800 Hardware Guide
Mount the RealPresence Collaboration Server 1800 on a Shelf
Follow the steps below to mount the system on a shelf.
1 Install the shelf supplied by the rack manufacturer, in the rack.
2 Mount the system on the shelf.
3 Fasten the system to the rack with screws through the four holes in the system's front mounting
brackets.
Connect the RealPresence Collaboration Server 1800 to a Power
Source
The following restrictions apply to the conductors and connectors that may be used to ground the unit when
rack mounted:
● When using bare conductors, they must be coated with an appropriate antioxidant compound before
crimp connections are made. Tinned, solder-plated or silver-plated connectors do not have to be
prepared in this manner.
● The same bolt assemblies should not secure multiple connectors.
● Listed fastening hardware must be compatible with the materials being joined and must be preclude
loosening, deterioration and electrochemical corrosion of the hardware and joint materials.
Connect the RealPresence Collaboration Server 1800 to AC Power
Only the AC Power cable supplied by Polycom should be used.
The size of the protective earthing conductor should be a minimum of 10 AWG.
The outlet intended for connecting the power cord must be protected with an external overcurrent
protection device either in building or in the rack with the rating not higher than 20 AMP.
Do not use an extension cord with the cable.
» Insert the power cable into the power connector on the rear panel of the RealPresence Collaboration
Server 1800 system.
To connect the cables:
1 Connect the management network cable to LAN 1 port.