Mounting The Realpresence Collaboration Server 1800 On A Shelf; Connecting The Realpresence Collaboration Server 1800 To A Power Source; Connecting The Realpresence Collaboration Server 1800 To Ac Power - Polycom Collaboration Server (RMX) 1800 Hardware Manual

Hide thumbs Also See for Collaboration Server (RMX) 1800:
Table of Contents

Advertisement

RealPresence Collaboration Server 1800 Hardware Guide

Mounting the RealPresence Collaboration Server 1800 on a Shelf

Connecting the RealPresence Collaboration Server 1800 to a Power Source

The following restrictions apply to the conductors and connectors that may be used to
ground the unit when rack mounted:

Connecting the RealPresence Collaboration Server 1800 to AC Power

Polycom, Inc.
— Install the shelf supplied by the rack manufacturer, in the rack.
— Mount the system on the shelf.
— Fasten the system to the rack with screws through the four holes in the system's
front mounting brackets.
When using bare conductors, they must be coated with an appropriate antioxidant
compound before crimp connections are made. Tinned, solder-plated or silver-plated
connectors do not have to be prepared in this manner.
The same bolt assemblies should not secure multiple connectors.
Listed fastening hardware must be compatible with the materials being joined and
must be preclude loosening, deterioration and electrochemical corrosion of the
hardware and joint materials.
Only the AC Power cable supplied by Polycom should be used.
The size of the protective earthing conductor should be a minimum of 10 AWG.
The outlet intended for connecting the power cord must be protected with an external
overcurrent protection device either in building or in the rack with the rating not higher than 20
AMP.
Do not use an extension cord with the cable.
Insert the power cable into the power connector on the rear panel of the RealPresence
Collaboration Server 1800 system.
8

Advertisement

Table of Contents
loading

Table of Contents