1.1

System Electrical Characteristics

Table 1-3: UPS Characteristics System Ratings.
Input
Power
Voltage
Rating
(VAC)
5 kVA
7 kVA
208
11 kVA
Table 1-4: Transformer Module Characteristics Ratings.
Input Voltage (VAC)
Output Voltage (VAC)
Max. Output Current (A)
CAUTION
86-86000-00 B01
UPS Characteristics
MAIN 1 (Normal AC Source) default
Input Current (A)
Min
Max
Online
18
32
21.6
25
45
30.3
38
64
44
Transformer Module Characteristics
120/120
33.3/33.3
Power Module is factory configured at 208Vac, 60 Hz input and output.
Without transformer, Input and Output of the UPS must always be
the same.
On 11KVA, 10% de-rating for 200/208VAC.
Isolated 120/208/240VAC are available with EX RT Transformer Module.
Introduction
Installation and User Manual
Input
Output
Breaker
Voltage
Bypass
(A)
19
40
26.65
50
42
70
208/240
208
52
Output
Inrush
Current
Current
(VAC)
(A)
19.25
208
23.5
200A/1ms
47.5
240
45
1 — 3