Multiple Battery Module Back-Up Time At Full Load; Battery Extension Cable Kit; Typical Back-Up Time With Multiple Exbs At Full Load - MGE UPS Systems EX 5 Installation And User Manual

Rt systems
Table of Contents

Advertisement

EX 5/7/11 RT Systems
1.5.3

Multiple Battery Module Back-up Time at Full Load

Standard EX 5/7/11 RT systems (one Power Module and one Battery Module), offers a standard back-up time of 5
to 12 minutes at full load.
To increase back-up time, it is possible to connect up to 5 additional Battery Modules to the standard system. See
Section 2.8 for connections between standard system and Battery Module (EXB 5/7/11RT)
Figure 1-9: Typical back-up time with multiple EXB's at full load.
Standard
EX 5/7/11RT systems
EX 5/7/11RT EXB 5/7/11RT
5 kVA :
7 kVA :
11 kVA:
See Appendix for additional Back-up time information.
1.5.4

Battery Extension Cable Kit

(6 ft./1.8 m, Part number 86006)
This extended battery cable kit will be used instead of the standard battery cable when Battery Modules (EXBs) are
distant from each other (located in two different enclosures, for instance).
The battery extension cable kit includes a 6 ft. long, straight connector battery power cable, and a 6 ft. long battery
detection cable.
86-86000-00 B01
EXB 5/7/11RT
EXB 5/7/11RT
9 min
25 min
7 min
20 min
5 min
14 min
Optional
Configurations
+
EXB 5/7/11RT
45 min
60 min
32 min
45 min
22 min
30 min
Introduction
Installation and User Manual
+
EXB 5/7/11RT
EXB 5/7/11RT
84 min
100 min
57 min
72 min
42 min
53 min
1 — 9