EX 5/7/11 RT Systems
Table 5-7: Efficiency on ECO Mode (All Kinds of Load) and Batteries Fully Charged.
kVA / kW
5kVA /
4kWatts
7kVA /
4.9kWatts
11kVA /
8kWatts
5.6

Heat Rejection

Table 5-8: Full Load Heat Rejection in BTUs/hr.
System
On-line
5kVA
1350
7kVA
1654
11kVA
3033
5.7

Environmental Characteristics

The operating temperature is 0 to 40°C (8 hours at 45°C), however optimum operation is within the +20 to
+25°C range and at 5-95% humidity, non-condensing at altitude up to 3280ft without de-rating.
The storage temperature: -20 to 40°C. Humidity: 5-95%, non condensing.
Battery back-up time is adversely affected by high and low temperatures. It is significantly reduced at temper-
atures under 10°C. Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery manufacturers
no longer guarantee operation due to the risk of thermal runaway.
Air enters through the front air vent grills and exits through the back. Always keep air vent grills unobstructed.
5 — 4
25%
50%
75%
100%
96
97
96
97
95
96
96
96
96
97
96
97
95
96
96
96
96
97
96
97
95
96
96
96
Operation Mode
On Battery
1861
2280
3723
Appendix
Output load percentage
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
86-86000-00 B01