Appendices; Technical Characteristics - MGE UPS Systems Pulsar EX 700RT Installation And User Manual

Table of Contents

Advertisement

6.1 Technical characteristics

AC INPUT
Output power rating
AC-input
Voltage
Frequency
Power factor
Output specification
Voltage
Frequency
Harmonic distortion
Overload capability
Output Receptacle
Power Share (#12 #2)
Battery (sealed lead-acid,
maintenance free)
Environmental and safety
Noise level
Operating temperature
Relative humidity
Safety
EMC
Agency markings
(1) Input voltage correspond to 33% / 66% / 100% of the nominal power rating.
(2) Adjustable from 100 V to 127 V using UPS Driver software.
(3) Frequency converter mode may be set using the UPS Driver software.
SAFETY
RELAY
EMI FILTER
BATTERY
POWER
CHARGER
SUPPLY
BATTERY
Pulsar EX 700RT
700 VA / 490 W
Single phase, 60 V / 70 V / 80 V to 142 V (1)
50/60 Hz (auto-select)
≥ 0.95
Single phase, 120 V ± 3% (2)
50/60 Hz ± 0.5% (3)
< 4% on linear load, < 6% on non linear load
110% continuous, 130% 12s, > 130% 1.5s
6-NEMA 15R
2-NEMA 15R
3 x 12 V - 7 Ah
< 45 dBA
0 to 40° C
20 to 90% (without condensation)
UL 1778 / cUL CSA 22.2 N°107.1
FCC 47 CFR Part 15, class B
UL , cUL
AC/DC PFC
DC/AC
CONVERTER
INVERTER
DC/DC
PUSH PULL
Pulsar EX 1500RT
Pulsar EX 1000RT
1500 VA / 1050 W
1000 VA / 700 W
6-NEMA 15/20R
2-NEMA 15/20R
3 x 12 V -9 Ah

6. Appendices

BYPASS
EMI FILTER
AC OUTPUT
RELAY
Pulsar EXB 1500RT
36VDC - 14 Ah
Runtime @ full load
20min -40min -60min -80min
1EXB -2EXB -3EXB -4EXB
QUALITY
ISO 9001 quality system.
36VDC - 14 Ah
UL, CSA
FCC Class B
UL , cUL
86-153850-00 A01
- Page 25

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pulsar ex 1000rtPulsar ex 1500rt

Table of Contents