Connection Of Optional Cla Module; Rear View Of Cla Module Cable Battery And Ac Input Connections - MGE UPS Systems EX 5 Installation And User Manual

Rt systems
Table of Contents

Advertisement

2.9

Connection of Optional CLA Module

1. Connect the battery power cable
between the Power Module and the CLA Module.
2. Connect the DC Input of the CLA Module to high power battery cabinet.
◗ DC Input Cable cross-section (not provided): maximum 4 AWG solid or stranded wire.
3. Connect the utility AC input to terminal blocks L1 and L2 of the CLA.
◗ AC input cable cross-section (not provided): maximum 16 AWG solid or stranded wires.
Field wiring connections to terminal block shall be made using the following:
– No. 14 AWG, 60ºC copper wires for AC inputs.
– No. 10 AWG, 75º C copper wires for DC inputs.
Figure 2-17: Rear view of CLA Module cable battery and AC input connections
Connection Diagram
(inside CLA Module)
-
+
DC INPUT
240Vdc
Terminal tightening torque:
– 5 lb-in. for AC input terminals
– 18 lb-in. for DC input terminals
86-86000-00 B01
40
and battery detection cable
N
L
(L2)
(L1)
AC INPUT
156-280Vac
DC Input to
High Power
Battery Cabinet
Separate, 15A Utility
AC Source
@ 208 or 240
Use 15A DBL. Pole CB
Installation
Installation and User Manual
42
(provided with the CLA Module)
42
40
2 — 19