6.1 Technical data
Output currents and voltage
Rated output current:
Input and output voltage:
Rated operating voltage:
Maximum voltage:
Minimum voltage:
Rated frequency:
Thermal characteristics
Heat losses
at rated power:
at 50% rated power:
Required ventilation:
(1) These characteristics are calculated for a voltage of 400 V and a power factor of 0.8.
Noise level
Noise in dB (ISO 3746):
Cable sizes
Cross-sectional area in mm
Recommended protection devices upstream of Upsilon STS
Type of circuit breaker:
TNS system:
TNC system:
Trip unit:
Thermal setting:
Magnetic setting:
Permissible-overload curve
32 In
16 In
8 In
4 In
2 In
In
0.01 s
During an overload, transfer between sources is disabled.
Overloads higher than 1.5 In are stored in memory. The alarm must be reset to return to normal operation.
All manuals and user guides at all-guides.com
(1)
:
350 m
2
:
C60L 32A
curve C
0.1 s
1 s
10 s
30 A
60 A
100 A
380 V / 400 V / 415 V
498 V (415 V +20%)
247 V (380 V -35%)
50 or 60 Hz (45 Hz minimum, 66 Hz maximum)
195 W
295 W
430 W
150 W
195 W
260 W
3
3
3
/h
350 m
/h
350 m
/h
55
55
55
50
50
50
NS100H 4P 4D
NS100H 3P
STR22SE
≤1.05 In
1.05 In
≤10xIn
10xIn
t(s)
100 s
1000 s
6. Appendix
160 A
250 A
400 A
615 W
920 W
1420 W
350 W
495 W
735 W
3
3
3
1600 m
/h
1600 m
/h
2300 m
/h
59
59
59
120
120
240
NS160H
NS250H
NS400H
4P 4D
4P 4D
4P 4D
NS160H
NS250H
NS400H
3P
3P
3P
STR22SE
STR22SE
STR23SE
≤1.05 In
≤1.05 In
≤1,05 In
≤10xIn
≤10xIn
≤10xIn
34020113EN/AA
600 A
2150 W
1070 W
3
2300 m
/h
59
240
NS630H
4P 4D
NS630H
3P
STR23SE
≤1.05 In
≤10xIn