Connecting the Adapter to
the Drive
ATTENTION: Risk of injury or death exists. The PowerFlex
!
drive may contain high voltages that can cause injury or death.
Remove power from the drive, and then verify power has been
discharged before installing or removing the adapter.
1. Remove power from the drive.
2. Use static control precautions.
3. Remove the drive cover or open the drive door.
4. Connect the Internal Interface cable to the DPI port on the drive and
then to the DPI connector on the adapter (see
5. Secure and ground the adapter to the drive (see
following:
– On a PowerFlex 70 drive, fold the Internal Interface cable behind the
adapter and mount the adapter on the drive using the four captive
screws.
– On a PowerFlex 700, PowerFlex 700H or PowerFlex 700S drive,
mount the adapter on the drive using the four captive screws.
Important: Tighten all screws to properly ground the adapter.
Recommended torque is 0.9 N m (8.0 lb in).
Installing the Adapter
Figure
2.2).
Figure
2.3) by doing the
20-COMM-M Modbus/TCP Adapter User Manual
Publication 20COMM-UM014C-EN-P
2-3