Output Relays - GE 489 Instruction Manual

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

7.2 HARDWARE FUNCTIONAL TESTS
0 to 1 mA ANALOG INPUTS:
1.
Alter the following setpoints:
S11 ANALOG I/O
S11 ANALOG I/O
S11 ANALOG I/O
Analog output values should be ±0.01 mA on the ammeter. Measured analog input values should be ±10 units. Force
2.
the analog outputs using the following setpoints:
S12 TESTING
TEST ANALOG OUTPUT
S12 TESTING
TEST ANALOG OUTPUT
Verify the ammeter readings as well as the measured analog input readings. View the measured values in:
A2 METERING DATA
ANALOG
EXPECTED
OUTPUT
AMMETER
FORCE
READING
VALUE
0%
0 mA
25%
0.25 mA
50%
0.50 mA
75%
0.75 mA
100%
1.00 mA
To verify the functionality of the output relays, perform the following steps:
1.
Using the setpoint:
S12 TESTING
TEST OUTPUT RELAYS
select and store values as per the table below, verifying operation
FORCE
OPERATION
SETPOINT
R1
7
NO
NC
R1 Trip
R2 Auxiliary
R3 Auxiliary
R4 Auxiliary
R5 Alarm
R6 Service
All Relays
No Relays
The R6 Service relay is failsafe or energized normally. Operating R6 causes it to de-energize.
NOTE
7-8
ANALOG INPUT1
ANALOG INPUT1:
ANALOG INPUT1
ANALOG INPUT1 MINIMUM:
ANALOG INPUT1
ANALOG INPUT1 MAXIMUM:
FORCE ANALOG OUTPUTS FUNCTION: "
ANALOG OUTPUT 1 FORCED VALUE:
ANALOG INPUTS
MEASURED AMMETER READING
(MA)
1
2
FORCE OPERATION OF RELAYS:
EXPECTED MEASUREMENT
(
FOR SHORT)
R2
R3
R4
NO
NC
NO
NC
NO
NC
NO NC
489 Generator Management Relay
"0-1 mA"
"0"
"1000" (repeat for Analog Inputs 2 to 4)
"0%" (enter %, repeat for Outputs 2 to 4)
EXPECTED
ANALOG INPUT
READING
3
4
0 units
250 units
500 units
750 units
1000 units
"R1 Trip"
R5
R6
R1
R2
NO
NC
NO NC NO
7 TESTING
Enabled"
MEASURED ANALOG INPUT
READING (UNITS)
1
2
3

7.2.9 OUTPUT RELAYS

ACTUAL MEASUREMENT
(
FOR SHORT)
R3
R4
R5
NC
NO
NC
NO
NC
NO
NC
GE Multilin
4
R6
NO
NC