GE 489 Instruction Manual page 35

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

3 USER INTERFACES
2.
Press the
or
VALUE
VALUE
3.
Repeat Step 2 for the remaining characters: e, n, e, r, a, t, o, r, #, and 1.
4.
Press
to store the text message.
ENTER
c) ENTERING +/– SIGNS
The 489 does not have a '+' or '–' key. Negative numbers may be entered in one of the following two ways:
Press the
or
VALUE
VALUE
Once a numeric setpoint is entered (after pressing at least one numeric key), press the
change the sign, if applicable.
d) SETPOINT ENTRY
To store setpoints with the keypad, Terminals C1 and C2 (access terminals) must be shorted (a key switch may be used for
security). There is also a setpoint passcode feature that can restrict setpoint access from the keypad and communication
ports. If activated, the passcode must be entered before changing the setpoint values. A passcode of "0" turns off the pass-
code feature and only the access jumper is required to change setpoints. If no setpoint changes are made for 30 minutes,
access to setpoint values will be restricted until the passcode is entered again. To prevent setpoint access before the 30
minutes expiry, the unit may be turned off and back on, the access jumper may be removed, or the
point may be changed to "Restricted". The passcode for the front panel keypad cannot be entered until terminals C1 and
C2 are shorted. The Setpoint Access LED Indicator will be on if setpoint access is enabled for the front panel keypad.
The following procedure may be used to access and alter any setpoint message. This specific example will refer to entering
a valid passcode in order to allow access to setpoints if the passcode was "489"
1.
The 489 programming is broken down into pages by logical groups. Press
until the desired page appears on the screen. Press
SETPOINTS
S1 489 SETUP
2.
Each page is broken further into subgroups. Press the
the desired subgroup appears on the screen. Press
PASSCODE
[ENTER] for more
3.
Each sub-group has one or more associated setpoint messages. Press the
through setpoint messages until the desired setpoint message appears on the screen.
ENTER PASSCODE FOR
ACCESS:
4.
The majority of setpoints may be may be altered by pressing the
appears then pressing
ENTER
point value is out of range, the original setpoint value reappears. If an out-of-step setpoint is entered, an adjusted value
is stored (e.g. a value of 101 for a setpoint that steps 95, 100, 105 is stored as 100). If a mistake is made entering the
new value, pressing
ESCAPE
Entering Alphanumeric Text on page 3–2. When a new setpoint is successfully stored, the
message flashes on the display.
STORED
5.
Press the 4, 8, and 9 keys, then press
and the display returns to:
SETPOINT ACCESS:
PERMITTED
6.
Press
to exit the subgroup. Pressing
ESCAPE
GE Multilin
key until "G" appears, then press the decimal key to advance the cursor.
keys the scroll through the setpoint range, including any negative numbers.
MESSAGE
MESSAGE
ENTER
. Numeric setpoints may also be entered directly through the keypad. If an entered set-
resets the setpoint to its original value. Text editing is described in detail in Section b):
. The
NEW SETPOINT HAS BEEN STORED
ESCAPE
numerous times always brings the cursor to the top of the page.
ESCAPE
489 Generator Management Relay
3.1 FACEPLATE INTERFACE
to cycle through the setpoint pages
SETPOINT
to enter a page.
and
keys to cycle through subgroups until
MESSAGE
to enter a subgroup.
MESSAGE
and
VALUE
VALUE
or
key to
VALUE
VALUE
set-
SETPOINT ACCESS
and
keys to cycle
MESSAGE
keys until the desired value
NEW SETPOINT HAS BEEN
message is briefly displayed
3-3
3