4.4 S3 DIGITAL INPUTS
PATH: SETPOINTS
S3 DIGITAL INPUTS
REMOTE RESET
[ENTER] for more
Once an input is assigned to the Remote Reset function, shorting that input will reset any latched trips or alarms that may
be active, provided that any thermal lockout time has expired and the condition that caused the alarm or trip is no longer
present.
If an input is assigned to the tachometer function, it may not be used here.
PATH: SETPOINTS
S3 DIGITAL INPUTS
TEST INPUT
[ENTER] for more
4
Once the 489 is in service, it may be tested from time to time as part of a regular maintenance schedule. The unit will have
accumulated statistical information relating historically to generator and breaker operation. This information includes: last
trip data, peak demand data, MWh and Mvarh metering, parameter averages, RTD maximums, analog input minimums and
maximums, number of trips, number of trips by type, number of breaker operations, the number of thermal resets, total gen-
erator running hours, and the event record. When the unit is under test and one of the inputs is assigned to the Test Input
function, shorting that input will prevent all of this data from being corrupted or updated.
If an input is assigned to the tachometer function, it may not be used here.
PATH: SETPOINTS
S3 DIGITAL INPUTS
THERMAL RESET
[ENTER] for more
During testing or in an emergency, it may be desirable to reset the thermal memory used to zero. If an input is assigned to
the Thermal Reset function, shorting that input will reset the thermal memory used to zero. All Thermal Resets will be
recorded as events.
If an input is assigned to the tachometer function, it may not be used here.
PATH: SETPOINTS
S3 DIGITAL INPUTS
DUAL SETPOINTS
[ENTER] for more
If an input is assigned to the tachometer function, it may not be used here.
This feature allows for dual settings for the current, voltage, power, RTD, and thermal model protection elements (setpoint
pages S5 to S9). These settings are organized in two setpoint groups: the main group (Group 1) and the alternate group
(Group 2). Only one group of settings are active in the protection scheme at a time.
4-16
REMOTE RESET
ð
ASSIGN DIGITAL
ENTER
ð
ESCAPE
INPUT: None
TEST INPUT
ð
ASSIGN DIGITAL
ENTER
ð
ESCAPE
INPUT: None
THERMAL RESET
ð
ASSIGN DIGITAL
ENTER
ð
ESCAPE
INPUT: None
DUAL SETPOINTS
ð
ASSIGN DIGITAL
ENTER
ð
ESCAPE
INPUT: None
ACTIVATE SETPOINT
ESCAPE
GROUP: Group 1
MESSAGE
EDIT SETPOINT
ESCAPE
GROUP: Group 1
MESSAGE
489 Generator Management Relay
4.4.4 REMOTE RESET
Range: None, Input 1, Input 2, Input 3, Input 4, Input 5,
Input 6, Input 7
Range: None, Input 1, Input 2, Input 3, Input 4, Input 5,
Input 6, Input 7
4.4.6 THERMAL RESET
Range: None, Input 1, Input 2, Input 3, Input 4, Input 5,
Input 6, Input 7
4.4.7 DUAL SETPOINTS
Range: None, Input 1, Input 2, Input 3, Input 4, Input 5,
Input 6, Input 7
Range: Group 1, Group 2
Range: Group 1, Group 2
4 SETPOINTS
4.4.5 TEST INPUT
GE Multilin