GE 489 Instruction Manual page 206

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

6.5 DNP POINT LISTS
Table 6–5: BINARY INPUT POINTS (SHEET 3 OF 4)
INDEX
DESCRIPTION
85
Loss of Excitation Circle 2 Trip Active
or Latched
86
Ground Directional Trip Active or
Latched
87
High Set Phase O/C Trip Active or
Latched
88
Distance Zone 1 Trip Active or Latched
89
Distance Zone 2 Trip Active or Latched
90
... Reserved ...
99
... Reserved ...
100
Assignable In 1 Alarm Active / Latched
101
Assignable In 2 Alarm Active or
Latched
102
Assignable In 3 Alarm Active or
Latched
103
Assignable In 4 Alarm Active or
Latched
104
Assignable In 5 Alarm Active or
Latched
105
Assignable In 6 Alarm Active or
Latched
106
Assignable In 7 Alarm Active / Latched
107
Tachometer Alarm Active or Latched
108
Overcurrent Alarm Active or Latched
109
Neg Seq Alarm Active or Latched
110
Ground O/C Alarm Active or Latched
6
111
Undervoltage Alarm Active or Latched
112
Overvoltage Alarm Active or Latched
113
Volts/Hertz Alarm Active or Latched
114
Underfreq Alarm Active or Latched
115
Overfrequency Alarm Active or
Latched
116
Neutral O/V (fundamental) Alarm
Active or Latched
117
Neutral U/V (3
Latched
118
Reactive Power Alarm Active or
Latched
119
Reverse Power Alarm Active or
Latched
120
Low Fwd Power Alarm Active /
Latched
121
RTD #1 Alarm Active or Latched
122
RTD #2 Alarm Active or Latched
123
RTD #3 Alarm Active or Latched
124
RTD #4 Alarm Active or Latched
125
RTD #5 Alarm Active or Latched
Any detected change in the state of any point assigned to Class 1 will cause the generation of an event object.
NOTE
6-44
EVENT
CLASS
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
rd
harm) Alarm Active or
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
489 Generator Management Relay
Table 6–5: BINARY INPUT POINTS (SHEET 4 OF 4)
INDEX
DESCRIPTION
126
RTD #6 Alarm Active or Latched
127
RTD #7 Alarm Active or Latched
128
RTD #8 Alarm Active or Latched
129
RTD #9 Alarm Active or Latched
130
RTD #10 Alarm Active or Latched
131
RTD #11 Alarm Active or Latched
132
RTD #12 Alarm Active or Latched
133
Open Sensor Alarm Active or Latched
134
Short/Low Temp Alarm Active /
Latched
135
Thermal Model Alarm Active or
Latched
136
Trip Counter Alarm Active or Latched
137
Breaker Failure Alarm Active or
Latched
138
Trip Coil Monitor Alarm Active /
Latched
139
VTFF Alarm Active or Latched
140
Current Dmd Alarm Active or Latched
141
MW Demand Alarm Active or Latched
142
Mar Demand Alarm Active or Latched
143
MVA Alarm Active or Latched
144
Analog Input 1 Alarm Active or
Latched
145
Analog Input 2 Alarm Active or
Latched
146
Analog Input 3 Alarm Active or
Latched
147
Analog Input 4 Alarm Active or
Latched
148
Not Programmed Alarm Active /
Latched
149
Simulation Mode Alarm Active or
Latched
150
Output Relays Forced Alarm Active or
Latched
151
Analog Output Forced Alarm Active or
Latched
152
Test Switch Shorted Alarm Active or
Latched
153
Gnd Directional Alarm Active or
Latched
154
IRIG-B Failure Alarm Active or Latched
155
Generator Running Hour Alarm Active
or Latched
6 COMMUNICATIONS
EVENT
CLASS
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1