Ge Multilin Hgf Ground Accuracy; Neutral Voltage (3Rd Harmonic) Accuracy - GE 489 Instruction Manual

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

7 TESTING
The specification for GE Multilin HGF 50:0.025 ground current input accuracy is ±0.5% of 2 × CT rated primary (25 A). Per-
form the steps below to verify accuracy.
1.
Alter the following setpoint:
S2 SYSTEM SETUP
CURRENT SENSING
Measured values should be ±0.25 A. Inject the values shown in the table below either as primary values into a GE Mul-
2.
tilin 50:0.025 Core Balance CT or as secondary values that simulate the core balance CT. Verify accuracy of the mea-
sured values in:
A2 METERING DATA
CURRENT METERING
INJECTED CURRENT
PRIMARY 50:0.025 CT
0.25 A
1 A
5 A
10 A
The 489 specification for neutral voltage (3rd harmonic) accuracy is ±0.5% of full scale (100 V). Perform the steps below to
verify accuracy.
1.
Alter the following setpoints:
S2 SYSTEM SETUP
VOLTAGE SENSING
S2 SYSTEM SETUP
VOLTAGE SENSING
S2 SYSTEM SETUP
GEN. PARAMETERS
Measured values should be ±5.0 V. Apply the voltage values shown in the table and verify accuracy of the measured
2.
values. View the measured values in:
A2 METERING DATA
VOLTAGE METERING
APPLIED NEUTRAL
VOLTAGE AT 180 HZ
10 V
30 V
50 V
GE Multilin
GROUND CT:
SECONDARY
0.125 mA
0.5 mA
2.5 mA
5 mA
NEUTRAL VOLTAGE TRANSFORMER:
NEUTRAL V.T. RATIO:
GENERATOR NOMINAL FREQUENCY:
EXPECTED NEUTRAL
MEASURED NEUTRAL
VOLTAGE
100 V
300 V
500 V
489 Generator Management Relay
7.3 ADDITIONAL FUNCTIONAL TESTS

7.3.6 GE MULTILIN HGF GROUND ACCURACY

"50:0.025 CT"
CURRENT READING
EXPECTED
MEASURED
0.25 A
1.00 A
5.00 A
10.00 A

7.3.7 NEUTRAL VOLTAGE (3RD HARMONIC) ACCURACY

"Yes"
"10.00:1"
"60 Hz"
VOLTAGE
7
7-13

Advertisement

Table of Contents
loading

Table of Contents