4 SETPOINTS
4.12S11 ANALOG I/O
PATH: SETPOINTS
S11 ANALOG I/O
ANALOG OUTPUT 1
[ENTER] for more
ANALOG OUTPUT 2
[ENTER] for more
ANALOG OUTPUT 3
[ENTER] for more
ANALOG OUTPUT 4
[ENTER] for more
The 489 has four analog output channels (4 to 20 mA or 0 to 1 mA as ordered). Each channel may be individually config-
ured to represent a number of different measured parameters as shown in the table below. The minimum value pro-
grammed represents the 4 mA output. The maximum value programmed represents the 20 mA output. All four of the
outputs are updated once every 50 ms. Each parameter may only be used once.
The analog output parameter may be chosen as Real Power (MW) for a 4 to 20 mA output. If rated power is 100 MW, the
minimum is set for 0.00 × Rated, and the maximum is set for 1.00 × Rated, the analog output channel will output 4 mA
when the real power measurement is 0 MW. When the real power measurement is 50 MW, the analog output channel will
output 12 mA. When the real power measurement is 100 MW, the analog output channel will output 20 mA.
GE Multilin
ANALOG OUTPUT 1(4)
ð
ANALOG OUTPUT 1:
ENTER
ð
ESCAPE
Real Power (MW)
REAL POWER (MW)
ESCAPE
MIN: 0.00 x Rated
MESSAGE
REAL POWER (MW)
ESCAPE
MAX: 1.25 x Rated
MESSAGE
ð
ANALOG OUTPUT 2:
ENTER
ð
Apparent Power (MVA)
ESCAPE
APPARENT POWER (MVA)
ESCAPE
MIN: 0.00 x Rated
MESSAGE
APPARENT POWER (MVA)
ESCAPE
MAX: 1.25 x Rated
MESSAGE
ð
ANALOG OUTPUT 3:
ENTER
ð
Avg. Output Current
ESCAPE
AVG. OUTPUT CURRENT
ESCAPE
MIN: 0.00 x FLA
MESSAGE
AVG. OUTPUT CURRENT
ESCAPE
MAX: 1.25 x FLA
MESSAGE
ð
ANALOG OUTPUT 4:
ENTER
ð
Average Voltage
ESCAPE
AVERAGE VOLTAGE
ESCAPE
MIN: 0.00 x Rated
MESSAGE
AVERAGE VOLTAGE
ESCAPE
MAX: 1.25 x Rated
MESSAGE
489 Generator Management Relay
4.12 S11 ANALOG I/O

4.12.1 ANALOG OUTPUTS 1 TO 4

Range: See Table 4–8: Analog Output Parameter
Selection on page 4–76.
Range: 0.00 to 2.00 × Rated in steps of 0.01
Range: 0.00 to 2.00 × Rated in steps of 0.01
Range: See Table 4–8: Analog Output Parameter
Selection on page 4–76.
Range: 0.00 to 2.00 × Rated in steps of 0.01
Range: 0.00 to 2.00 × Rated in steps of 0.01
Range: See Table 4–8: Analog Output Parameter
Selection on page 4–76.
Range: 0.00 to 20.00 × Rated in steps of 0.01
Range: 0.00 to 20.00 × Rated in steps of 0.01
Range: See Table 4–8: Analog Output Parameter
Selection on page 4–76.
Range: 0.00 to 1.50 × Rated in steps of 0.01
Range: 0.00 to 1.50 × Rated in steps of 0.01
4
4-75