GE 489 Instruction Manual page 195

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

6 COMMUNICATIONS
Table 6–1: 489 MEMORY MAP (SHEET 24 OF 24)
ADDR NAME
30E2
HOTTEST OTHER RTD TEMPERATURE
30E3
HOTTEST AMBIENT RTD TEMPERATURE
30E5
NEUTRAL VOLT (FUND)
30E7
NEUTRAL VOLT (3rd)
30E9
Vab/Iab
30EA
Vab/Iab ANGLE
WAVEFORM MEMORY SETUP
30F0
WAVEFORM MEMORY TRIGGER DATE
30F2
WAVEFORM MEMORY TRIGGER TIME
30F4
FREQUENCY DURING TRACE ACQUISITION
30F5
WAVEFORM MEMORY CHANNEL SELECTOR
(HOLDING REGISTER)
30F6
WAVEFORM TRIGGER SELECTOR
30F7
WAVEFORM TRIGGER CAUSE (READ-ONLY)
30F8
NUMBER OF SAMPLES PER WAVEFORM CAPTURE
30F9
NUMBER OF WAVEFORM CAPTURES TAKEN
WAVEFORM MEMORY SAMPLES
3100
FIRST WAVEFORM MEMORY SAMPLE
3400
LAST WAVEFORM MEMORY SAMPLE
1, 2, 3
See Table footnotes on page 6–33
1.
Value of 65535 indicates 'Never'
2.
A value of 0xFFFF indicates "no measurable value".
3.
Maximum value turns feature 'Off'
GE Multilin
RANGE
–50 to 250
–50 to 250
0 to 250000
0 to 250000
0 to 65535
0 to 359
N/A
N/A
0 to 12000
0 to 9
1 to 65535
0 to 139
1 to 768
0 to 65535
–32767 to 32767
–32767 to 32767
489 Generator Management Relay
6.3 MODBUS MEMORY MAP
STEP
UNITS
FORMAT
1
°F
F4
1
°F
F4
1
Volts
F10
1
Volts
F10
1
ohms s
F1
1
°
F1
N/A
N/A
F18
N/A
N/A
F19
1
Hz
F3
1
N/A
F214
1
N/A
F1
1
N/A
F134
1
N/A
F1
1
N/A
F1
1
N/A
F4
1
N/A
F4
DEFAULT
0
0
0
0
0
0
N/A
N/A
0
0
0
0
168
0
0
0
6
6-33

Advertisement

Table of Contents
loading

Table of Contents