6 COMMUNICATIONS
Table 6–2: DATA FORMATS (SHEET 2 OF 5)
FORMAT
TYPE
DEFINITION
CODE
F107
Unsigned
Nominal frequency selection
16 bit integer
0 = -----, 1 = 60 Hz, 2 = 50 Hz, 3 = 25 Hz
F109
Unsigned
Breaker status switch type
16 bit integer
0 = Auxiliary a, 1 = Auxiliary b
F115
Unsigned
Alarm / trip type selection
16 bit integer
0 = Off, 1 = Latched, 2 = Unlatched
F117
Unsigned
Reset mode
16 bit integer
0 = All Resets, 1 = Remote Reset Only
F118
Unsigned
Setpoint Group
16 bit integer
0 = Group 1, 1 = Group 2
F120
Unsigned
RTD type
16 bit integer
0 = 100 Ohm Platinum, 1 = 120 Ohm Nickel, 2 = 100 Ohm Nickel, 3 = 10 Ohm Copper
F121
Unsigned
RTD application
16 bit integer
0 = None, 1 = Stator, 2 = Bearing, 3 = Ambient, 4 = Other
F122
Unsigned
RTD voting selection
16 bit integer
1 = RTD #1, 2 = RTD #2, 3= RTD #3,..., 12 = RTD #12
F123
Unsigned
Alarm / trip status
16 bit integer
0 = Not Enabled, 1 = Inactive, 2 = Timing Out, 3 = Active Trip, 4 = Latched Trip
F124
Unsigned
Phase rotation selection
16 bit integer
0 = ----, 1 = ABC, 2 = ACB
F126
Unsigned
Disabled / Enabled selection
16 bit integer
0 = Disabled, 1 = Enabled
F127
Unsigned
Analog output parameter selection
16 bit integer
VALUE
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
F128
Unsigned
Overcurrent curve style selection
16 bit integer
VALUE
0
1
2
3
4
5
6
F129
Unsigned
Analog input selection
16 bit integer
0 = Disabled, 1 = 4-20 mA, 2 = 0-20 mA, 3 = 0-1 mA
F130
Unsigned
Pickup type
16 bit integer
0 = Over, 1 = Under
GE Multilin
PARAMETER
VALUE
None
22
IA Output Current
23
IB Output Current
24
IC Output Current
25
Avg. Output Current
26
Neg. Seq. Current
27
Averaged Gen. Load
28
Hottest Stator RTD
29
Hottest Bearing RTD
30
Ambient RTD
31
RTD #1
32
RTD #2
33
RTD #3
34
RTD #4
35
RTD #5
36
RTD #6
37
RTD #7
38
RTD #8
39
RTD #9
40
RTD #10
41
RTD #11
42
RTD #12
PARAMETER
VALUE
ANSI Extremely Inverse
7
ANSI Very Inverse
8
ANSI Normally Inverse
9
ANSI Moderately Inverse
10
IEC Curve A (BS142)
11
IEC Curve B (BS142)
12
IEC Curve C (BS142)
13
489 Generator Management Relay
6.3 MODBUS MEMORY MAP
PARAMETER
AB Voltage
BC Voltage
CA Voltage
Average Voltage
Volts / Hertz
Frequency
Neutral Voltage (3rd)
Power Factor
Reactive Power (Mvar)
Real Power (MW)
Apparent Power (MVA)
Analog Input 1
Analog Input 2
Analog Input 3
Analog Input 4
Tachometer
Therm. Capacity Used
Current Demand
Mar Demand
MW Demand
MVD Demand
PARAMETER
IEC Short Inverse
IAC Extremely Inverse
IAC Very Inverse
IAC Inverse
IAC Short Inverse
Flexcurve™
Definite Time
6