5.6 A5 EVENT RECORDER
The 489 Event Recorder stores generator and system information each time an event occurs. The description of the event
is stored and a time and date stamp is also added to the record. This allows reconstruction of the sequence of events for
troubleshooting. Events include: all trips, any alarm optionally (except Service Alarm, and 489 Not Inserted Alarm, which
always records as events), loss of control power, application of control power, thermal resets, simulation, serial communica-
tion starts/stops and general input control functions optionally.
is the most recent event and
EVENT01
until the 40th event is reached. The 40th event record is lost when the next event occurs. This information can be cleared
using
S1 489 SETUP
programmed as Test Input is shorted.
Table 5–1: CAUSE OF EVENTS
TRIPS
Ambient RTD12 Trip *
Bearing RTD 9 Trip *
Distance Zone 2 Trip
5
Hiset Phase O/C Trip
Low Fwd Power Trip
Offline O/C Trip
Phase Reversal Trip
Sequential Trip
Stator RTD 4 Trip *
Thermal Model Trip
ALARMS (OPTIONAL EVENTS)
Ambient RTD12 Alarm *
Bearing RTD 9 Alarm *
Gnd Directional Alarm
MVA Alarm
Neut. U/V 3rd Alarm
Overfrequency Alarm
RTD11 Alarm *
Stator RTD 3 Alarm
Tachometer Alarm
Underfrequency Alarm
OTHER
489 Not Inserted
Input A to G Control *
Serial Waveform Trip
Simulation Stopped
*
reflects the name that is programmed
5-24
ANALOG INPUT 2
ESCAPE
EVENT01: 0.0 Units
MESSAGE
ANALOG INPUT 3
ESCAPE
EVENT01: 0.0 Units
MESSAGE
ANALOG INPUT 4
ESCAPE
EVENT01: 0.0 Units
MESSAGE
is the oldest event. Each new event bumps the other event records down
EVENT40
CLEAR DATA
CLEAR EVENT RECORD
Analog I/P 1 to 4 Trip *
Bearing RTD 10 Trip *
Field-Bkr Discr. Trip
Input A to G Trip *
Neg Seq O/C Trip
Overfrequency Trip
Reactive Power Trip
Stator RTD 1 Trip *
Stator RTD 5 Trip *
Underfrequency Trip
Analog I/P 1 to 4 Alarm *
Bearing RTD 10 Alarm *
Ground O/C Alarm
Mvar Alarm
Neutral O/V Alarm
Overvoltage Alarm
Short/Low RTD Alarm
Stator RTD 4 Alarm
Thermal Model Alarm
Undervoltage Alarm
Control Power Applied
IRIG-B Failure
Setpoint 1 Active
Thermal Reset Close
489 Generator Management Relay
Range: –50000 to 50000
Seen only if the Analog Input is in use.
Range: –50000 to 50000
Seen only if the Analog Input is in use.
Range: –50000 to 50000
Seen only if the Analog Input is in use.
setpoint. The event record will not update if a digital input
Bearing RTD 7 Trip *
Differential Trip
Gnd Directional Trip
Loss of Excitation 1
Neutral O/V Trip
Overvoltage Trip
Reverse Power Trip
Stator RTD 2 Trip *
Stator RTD 6 Trip *
Undervoltage Trip
Bearing RTD 7 Alarm *
Breaker Failure
Input A to G Alarm *
MW Alarm
Open RTD Alarm
Reactive Power Alarm
Stator RTD 1 Alarm
Stator RTD 5 Alarm
Trip Coil Monitor
VT Fuse Fail Alarm
Control Power Lost
Serial Comm. Start
Setpoint 2 Active
Thermal Reset Open
5 ACTUAL VALUES
Bearing RTD 8 Trip *
Distance Zone 1 Trip
Ground O/C Trip
Loss of Excitation 2
Neut. U/V (3rd) Trip
Phase O/C Trip
RTD11 Trip *
Stator RTD 3 Trip *
Tachometer Trip
Volts/Hertz Trip
Bearing RTD 8 Alarm *
Current Demand Alarm
Low Fwd Power Alarm
NegSeq Current Alarm
Overcurrent Alarm
Reverse Power Alarm
Stator RTD 2 Alarm
Stator RTD 6 Alarm
Trip Counter Alarm
Dig I/P Waveform Trig
Serial Comm. Stop
Simulation Started
GE Multilin