4 SETPOINTS
4.11S10 MONITORING
PATH: SETPOINTS
S10 MONITORING

TRIP COUNTER

[ENTER] for more
When enabled, a trip counter alarm will occur when the
cleared or the alarm level raised and the reset key must be pressed (if the alarm was latched) to reset the alarm.
For example, it might be useful to set a Trip Counter alarm at 100 trips, prompting the operator or supervisor to investigate
the type of trips that have occurred. A breakdown of trips by type may be found in the
actual values page. If a trend is detected, it would warrant further investigation.
PATH: SETPOINTS
S10 MONITORING

BREAKER FAILURE

[ENTER] for more
If the breaker failure alarm feature may be enabled as latched or unlatched. If the R1 Trip output relay is operated and the
generator current measured at any of the three output CTs is above the level programmed for the period of time specified
by the delay, a breaker failure alarm will occur. The time delay should be slightly longer than the breaker clearing time.
GE Multilin
TRIP COUNTER
ð
TRIP COUNTER
ENTER
ð
ESCAPE
ALARM: Off
ASSIGN ALARM
ESCAPE
RELAYS (2-5): ---5
MESSAGE
TRIP COUNTER ALARM
ESCAPE
LEVEL: 25 Trips
MESSAGE
TRIP COUNTER ALARM
ESCAPE
EVENTS: Off
MESSAGE
TRIP COUNTER ALARM LEVEL
BREAKER FAILURE
ð
BREAKER FAILURE
ENTER
ð
ALARM: Off
ESCAPE
ASSIGN ALARM
ESCAPE
RELAYS (2-5): ---5
MESSAGE
BREAKER FAILURE
ESCAPE
LEVEL: 1.00 x CT
MESSAGE
BREAKER FAILURE
ESCAPE
DELAY: 100 ms
MESSAGE
BREAKER FAILURE
ESCAPE
ALARM EVENTS: Off
MESSAGE
489 Generator Management Relay
4.11 S10 MONITORING
4.11.1 TRIP COUNTER
Range: Off, Latched, Unlatched
Range: Any combination of Relays 2 to 5
Range: 1 to 50000 Trips in steps of 1
Range: On, Off
is reached. The trip counter must be
A4 MAINTENANCE
4.11.2 BREAKER FAILURE
Range: Off, Latched, Unlatched
Range: Any combination of Relays 2 to 5
Range: 0.05 to 20.00 × CT in steps of 0.01
Range: 10 to 1000 ms in steps of 10
Range: On, Off
TRIP COUNTERS
4
4-69