Pulse Output; Generator Running Hour Setup - GE 489 Instruction Manual

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

4.11 S10 MONITORING
PATH: SETPOINTS
S10 MONITORING

PULSE OUTPUT

[ENTER] for more
4
The 489 can perform pulsed output of positive kWh and both positive and negative kvarh. Each output parameter can be
assigned to any one of the alarm or auxiliary relays. Pulsed output is disabled for a parameter if the relay setpoint is
selected as OFF for that pulsed output. The minimum time between pulses is fixed to 400 milliseconds.
This feature should be programmed so that no more than one pulse per 600 milliseconds is required or the pulsing
will lag behind the interval activation. Do not assign pulsed outputs to the same relays as alarms and trip functions.
NOTE
PATH: SETPOINTS
S10 MONITORING
RUNNING HOUR SETUP
[ENTER] for more
The 489 can measure the generator running hours. This value may be of interest for periodic maintenance of the generator.
The initial generator running hour allows the user to program existing accumulated running hours on a particular generator
the relay is protecting. This feature switching 489 relays without losing previous generator running hour values.
4-74
PULSE OUTPUT
ð
POS. kWh PULSE OUT
ENTER
ð
RELAYS (2-5): ----
ESCAPE
POS. kWh PULSE OUT
ESCAPE
INTERVAL: 10 kWh
MESSAGE
POS. kvarh PULSE OUT
ESCAPE
RELAYS (2-5): ----
MESSAGE
POS. kvarh PULSE OUT
ESCAPE
INTERVAL: 10 kvarh
MESSAGE
NEG. kvarh PULSE OUT
ESCAPE
RELAYS (2-5): ----
MESSAGE
NEG. kvarh PULSE OUT
ESCAPE
INTERVAL: 10 kvarh
MESSAGE
PULSE WIDTH:
ESCAPE
200 ms
MESSAGE
normally open (NO) contact
normally closed (NC) contact
Figure 4–22: PULSE OUTPUT
RUNNING HORU SETUP
ð
INITIAL GEN. RUNNING
ENTER
ð
ESCAPE
HOURS: 0 h
GEN. RUNNING HOURS
ESCAPE
ALARM: Off
MESSAGE
ASSIGN ALARM
ESCAPE
RELAYS (2-5): ---5
MESSAGE
GEN. RUNNING HOURS
ESCAPE
LIMIT: 1000 h
MESSAGE
489 Generator Management Relay
Range: Any combination of Relays 2 to 5
Range: 1 to 50000 kWh in steps of 1
Range: Any combination of Relays 2 to 5
Range: 1 to 50000 kvarh in steps of 1
Range: Any combination of Relays 2 to 5
Range: 1 to 50000 kvarh in steps of 1
Range: 200 to 1000 ms in steps of 1
status
status
OPEN
CLOSED
CLOSED
OPEN
PULSE
WIDTH

4.11.7 GENERATOR RUNNING HOUR SETUP

Range: 0 to 999999 h in steps of 1
Range: Off, Latched, Unlatched
Range: Any combination of Relays 2 to 5
Range: 1 to 1000000 h in steps of 1
4 SETPOINTS
4.11.6 PULSE OUTPUT
status
OPEN
CLOSED
808738A1.CDR