AN-50 Terminal 42 Output

Option:
[0] *
No operation
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor Current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[113]
Ext. Closed Loop 1
[114]
Ext. Closed Loop 2
[115]
Ext. Closed Loop 3
[130]
Output freq. 4-20mA
[131]
Reference 4-20mA
[132]
Feedback 4-20mA
[133]
Motor cur. 4-20mA
[134]
Torq.% lim 4-20 mA
[135]
Torq.% nom 4-20mA
[136]
Power 4-20mA
[137]
Speed 4-20mA
[139]
Bus ctrl.
[140]
Bus ctrl. 4-20 mA
[141]
Bus ctrl t.o.
[142]
Bus ctrl t.o. 4-20mA
[143]
Ext. CL 1 4-20mA
[144]
Ext. CL 2 4-20mA
[145]
Ext. CL 3 4-20mA
NB!
Values for setting the Minimum Reference is found in open loop par. F-52 Minimum Reference and for closed loop par. CL-13 Minimum Reference/Feedb. - values
for maximum reference for open loop is found in par. F-53 Maximum Reference and for closed loop par. CL-14 Maximum Reference/Feedb..

AN-51 Terminal 42 Output Min Scale

Range:
0.00 %*
[0.00 - 200.00 %]
Function:
Select the function of Terminal 42 as an analog current output.
0 - 100 Hz
Minimum reference - Maximum reference
-200% to +200% of par. 20-14
: 0 - Inverter Max. Current (par. DR-37 Drive Max. Current)
: 0 - Torque limit (par. F-40 Torque Limiter (Driving))
: 0 - Motor rated torque
0 - Motor rated power
0 - Speed High Limit (par. F-17 Motor Speed High Limit [RPM] and par. F-15 Motor Speed High Limit [Hz])
0 - 100%
0 - 100%
0 - 100%
0 - 100 Hz
Minimum Reference - Maximum Reference
-200% to +200% of par. 2-14
0 - Inverter Max. Current (par. DR-37 Drive Max. Current)
:0 - Torque limit (par. F-40 Torque Limiter (Driving))
0 - Motor rated torque
0 - Motor rated power
0 - Speed High Limit (par. 4-13 and par. 4-14)
0 - 100%
0 - 100%
0 - 100%
0 - 100%
0 - 100%
0 - 100%
0 - 100%
Function:
Scale for the minimum output (0 or 4 mA) of the analogue signal at terminal 42.
Set the value to be the percentage of the full range of the variable selected in par. AN-50 Terminal 42
Output.
AF-600 FP High Power Operating Instructions
7
93