A5 Event Recorder; Event Recorder - GE 489 Instruction Manual

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

5 ACTUAL VALUES

5.6A5 EVENT RECORDER

PATH: ACTUAL VALUES
A5 EVENT RECORDER
[ENTER] EVENT01
No Event
GE Multilin
[ENTER] EVENT01(40)
ð
TIME OF EVENT01:
ENTER
ð
ESCAPE
00:00:00.0
DATE OF EVENT01:
ESCAPE
Jan. 01, 1992
MESSAGE
ACTIVE
ESCAPE
GROUP EVENT01: 1
MESSAGE
TACHOMETER
ESCAPE
EVENT01: 3600 RPM
MESSAGE
A:
0
B:
ESCAPE
C:
0
A
EVENT01
MESSAGE
a:
0
b:
ESCAPE
c:
0
A
EVENT01
MESSAGE
NEG. SEQ. CURRENT
ESCAPE
EVENT01: 0% FLA
MESSAGE
GROUND CURRENT
ESCAPE
EVENT01: 0.00 A
MESSAGE
Vab:
0
Vbc:
ESCAPE
Vca:
0
V
EVENT01
MESSAGE
FREQUENCY
ESCAPE
EVENT01: 0.00 Hz
MESSAGE
NEUTRAL VOLT (FUND)
ESCAPE
EVENT01:
MESSAGE
NEUTRAL VOLT (3rd)
ESCAPE
EVENT01:
MESSAGE
Vab/Iab EVENT01:
ESCAPE
0.0 Ωsec.
MESSAGE
REAL POWER (MW)
ESCAPE
EVENT01:
MESSAGE
REACTIVE POWER Mvar
ESCAPE
EVENT01:
MESSAGE
APPARENT POWER MVA
ESCAPE
EVENT01:
MESSAGE
HOTTEST STATOR
ESCAPE
RTD#1: 0°C
EVENT01
MESSAGE
HOTTEST BEARING
ESCAPE
RTD#7: 0°C
EVENT01
MESSAGE
HOTTEST OTHER
ESCAPE
RTD#11: 0°C
EVENT01
MESSAGE
AMBIENT
ESCAPE
RTD#12 0°C
EVENT01
MESSAGE
ANALOG INPUT 1
ESCAPE
EVENT01: 0.0 Units
MESSAGE
489 Generator Management Relay
5.6 A5 EVENT RECORDER
Range: hour:minutes:seconds
Seen only if there has been an event.
Range: month day, year
Seen only if there has been an event.
Range: 1, 2
Range: 0 to 3600 RPM. Seen only if a Digital Input is
programmed as Tachometer
Range: 0 to 999999 A. Represents current measured
0
from the output CTs. Seen only if there has been
an event.
Range: 0 to 999999 A. Represents differential current.
0
Seen only if the differential element is enabled.
Range: 0 to 2000% FLA
Seen only if there has been an event.
Range: 0.00 to 20000.0 A. Not seen if the
TYPE
is programmed as "None".
Range: 0 to 50000 V. Not seen if
0
programmed as "None".
Range: 0.00 to 90.00 Hz. Not seen if
is programmed as "None".
Range: 0.0 to 25000.0 V. Seen only if there is a neutral
voltage transformer.
0.0 V
Range: 0.0 to 25000.0 V. Seen only if there is a neutral
voltage transformer.
0.0 V
Range: 0.0 to 6553.5 Ωsec., 0 to 359°. Seen only if the
Loss of Excitation element is Enabled.
Range: 0.000 to ±2000.000 MW. Not seen if
CONNECTION
0.000
Range: 0.000 to ±2000.000 Mvar. Not seen if
CONNECTION
0.000
Range:0.000 to 2000.000 MVA. Not seen if
CONNECTION
0.000
Range: –50 to +250°C. Seen only if 1 or more RTDs are
programmed as Stator.
Range: –50 to +250°C. Seen only if 1 or more RTDs are
programmed as Bearing.
Range: –50 to +250°C. Seen only if 1 or more RTDs are
programmed as Other.
Range: –50 to +250°C. Seen only if 1 or more RTDs are
programmed as Ambient.
Range: –50000 to 50000
Seen only if the Analog Input is in use.

5.6.1 EVENT RECORDER

GROUND CT
VT CONNECTION
is
VT CONNECTION
VT
is programmed as "None"
VT
is programmed as "None"
VT
is programmed as "None"
5-23