Connecting Detection Devices To Panel Zone Inputs; Connecting Intrusion Detection Devices; Connecting 2-Wire Smoke Detectors - GE 60-960-95 Installation Instructions Manual

Concord ultra
Hide thumbs Also See for 60-960-95:
Table of Contents

Advertisement

Note
The panel comes with fac-
tory programmed onboard
hardwire zones. Install
2k-ohm, end of line (EOL)
resistors on all unused fac-
tory programmed onboard
hardwire zones. If you don't
want to install EOL resistors,
delete any unused zones
from memory. See Table 8
for onboard hardwire zone
factory programming.
11

Connecting Detection Devices to Panel Zone Inputs

Zone inputs 1 through 8 are supervised using included 2k-ohm, end-of-line resistors at the last
device on each circuit. All eight zones accept either normally open (N/O) or normally closed (N/
C) detection devices.

Connecting Intrusion Detection Devices

The graphics in Figure 7 show the typical wiring for N/C and N/O door/window intrusion detec-
tion and for a Detection Systems model DS922 (part no. 13-082) motion detector. The minimum
available panel voltage for hardwired PIR motion detectors is 8.5 VDC (9.5 VDC for UL listed
installations).
Note
When using 2-wire smoke detectors on zone 8, the Two-Wire Smoke setting (in program mode) must be
turned on before entering the
"Programming the Panel" for complete details.
Panel Terminals
Zone 2 GND Zone 3
Normally
Closed
(N/C)
Normally Open
Contacts
(N/O) Contacts in
In Series
2k Ohm EOL
Resistor 49-454
2k Ohm EOL
Resistor 49-454

Connecting 2-Wire Smoke Detectors

Zone input 8 can be set up (in program mode) to accept the following 12 VDC, 2-wire smoke
detectors:
System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400, 2400TH
ESL models 429AT, 521B, 521BXT—(models 521B and 521BXT require the following dip
switch settings: 1-on, 2-off)
!
Use only the 2-wire smoke detector models described above. Alarm signals from other
detectors may not be processed correctly if the panel has lost AC power and is operat-
ing only from the backup battery.
Caution
When set up for 2-wire smoke detectors, zone 8 can handle up to 10 smoke detectors with
120 uA maximum idle current per detector. Maximum total loop current allowed in an alarm con-
dition is 100 mA. Connect one or more, 2-wire smoke detectors to the panel as shown in
Figure 8.
menu. See
LEARN SENSORS
Parallel
Figure 7. Wiring Intrusion Detection
in the section
ONBOARD OPTIONS
INPUTS
+12
Zone
GND
BUS
Panel
Terminals
Motion
Detector
2k Ohm EOL Resistor 49-454
(Locate at Sensor)
7
Concord Ultra