Note
Insert the top left screw as
far as possible into the wall,
leaving enough room to
hang the panel on it. After
the panel is hung, you will
be unable to tighten this
screw.
Concord Ultra
Table 3: Minimum Device Current Draw
SuperBus 2000 Automation Module
SuperBus 2000 Transceiver Module
SuperBus 2000 Wireless Gateway Module
Interrogator 200
Interrogator AVM
After determining panel location, run all necessary wires to that location using the guidelines in
Table 4.
Device
AC Power Transformer
Earth Ground
Telephone (RJ-31X)
Detection Devices
Speakers
SuperBus 2000 Devices
Interrogator 200 AVM Power and Microphone 4-conductor, 22-gauge, shielded
2-Wire Smoke Detectors

Mounting the Panel

Use the following procedure to mount the panel to the wall or wall studs.
Make sure you are free of static electricity whenever you work on the panel with the cover
!
open. To discharge any static, first touch the metal panel chassis, then stay in contact with
the chassis when touching the circuit board. Using an approved grounding strap is recom-
mended.
Caution
¾
To mount the panel:
1.
Open the panel door and remove the necessary wiring knockouts (see Figure 2). Be careful
not to damage the circuit board.
2.
Feed all wires through wiring knockouts and place the panel in position against the wall.
3.
Level the panel and mark the top right and bottom mounting holes (see Figure 2). You will
be unable to mark the top left mounting hole.
4.
Make a level mark 10 inches to the left of the top right mounting mark. This will be the posi-
tion of the top left mounting screw.
5.
Install anchors where studs are not present.
6.
Partially insert screws into the two top mounting hole locations, then hang the panel on the
two screws.
7.
Recheck for level, insert the two lower screws, and tighten the top right and lower mounting
screws.
Device
Table 4: Wire Requirements
2-conductor, 18-gauge, 25 feet max
Single conductor, 16-gauge solid, 25 feet max
4-conductor
2- or 4-conductor, 18- to 22-gauge, 300-ohms
max loop resistance including device
2-conductor, 22-gauge, 175 feet max
2-conductor, 18-gauge, 440 feet max
4-conductor, 22- or 18-gauge
2-conductor, 22-gauge, 330 feet max
2-conductor, 18-gauge, 830 feet max
(based on 10-ohms max loop resistance plus
a 2k-ohm, end-of-line resistor)
Min. mA Draw
30 mA
50 mA
55 mA
10 mA
45 mA
Wire Requirements