Entering a Community String

To enter a read community or write community string using the Web-based user interface:
1. Click the Enclosure tab.
2. Click SNMP Configuration in the left panel.
3. Click the Read Community or Write Community field.
4. Type the string.
Entering a blank string into the Read Community field sets the Read Community to "public."
Entering a blank string into the Write Community field disables the SNMP set commands.
5. Click Apply.
To enter a read community or write community string using the CLI, type:
SET SNMP COMMUNITY [READ | WRITE] <community name>
The write <community name> must be 0-20 characters long and the read <community name>
must be 1-20 characters long. Both community names support all alphanumeric characters, the
underscore, and the dash characters.
The default read community name is "public," and the default write community name is blank.

Modifying the System Location

The SNMP protocol can be disabled in the Network Configuration area of the Web-based user
interface.
To modify the system location information using the Web-based user interface:
1. Click the Enclosure tab.
2. Click SNMP Configuration in the left panel.
3. Set the cursor in the System Location field and type the appropriate information.
4. Click Apply.
To modify the system location information using the CLI, type:
SET SNMP LOCATION <location>
The <location> field must be 0-20 characters long and supports all the alphanumeric characters,
the underscore, the dash, and spaces with quotes.

Modifying the System Contact Information

To modify the system contact information using the Web-based user interface:
1. Click the Enclosure tab.
2. Click SNMP Configuration in the left panel.
3. Set the cursor in the System Contact field and type the appropriate information.
4. Click Apply.
HP PC Blade Enclosure Integrated Administrator for CCI v1.4 User Guide
Setting Up the System
6-15