Entry Delay (0310)
This setting determines how much time (30-240 seconds) users have to disarm
the system (after entering the armed premises through a designated delay
door) to avoid causing an alarm.
Note
For UL Listed residential installations, the Entry Delay must be set to 45 seconds or
less. The combined time for the Entry Delay and Dialer Abort Delay (02006) must
not exceed 60 seconds.
Exit Delay (0311)
This setting determines how much time (45-184 seconds) the user has to leave
the premises through a designated delay door (after arming the system) with-
out causing an alarm.
Note
For UL Listed residential installations, the Exit Delay must be set to 60 seconds or
less.
Extended Delay (0312)
This setting determines how much time (1-8 minutes) the user has to enter or
exit the premises through a designated extended delay door without causing
an alarm.
Note
For UL Listed systems, Extended Delay shall not be used.
Siren Timeout (0313)
This setting determines how long sirens sound (1-30 minutes) if no one is
present to disarm the system.
Note
For UL Listed systems, Siren Timeout must be set to 4 minutes or more.
Fire Panic (0400)
This setting determines whether touchpad fire panic buttons are enabled (on)
or disabled (off).
31
Touchpad Options Menu
The
menu lets you set up touchpad panic and arming operation. The fol-
TOUCHPAD OPTIONS
lowing describes how to program the touchpad option settings that appear under
Timers-Partition 1 (Default=30 sec.)
¾
To set the Entry Delay:
1. With the display showing
(current setting), enter the desired
SECONDS
time value (30-240 using 8-second inter-
vals). The display flashes the entered set-
ting.
ƒ
2. Press
and the display shows the new set-
ting.
Timers-Partition 1 (Default=60 sec.)
¾
To set the Exit Delay:
1. With the display showing
(current setting), enter the desired
SECONDS
time value (45-184 using 8-second inter-
vals). The display flashes the entered set-
ting.
ƒ
2. Press
and the display shows the new set-
ting.
Timers-Partition 1 (Default=4 min.)
¾
To set the Extended Delay:
1. With the display showing
(current setting), enter the
nn MINUTES
desired time value (1-8). The display flashes
the entered setting.
ƒ
2. Press
and the display shows the new set-
ting.
Timers-Partition 1 (Default=4 min.)
¾
To set the Siren Timeout:
1. With the display showing
(current setting), enter the desired
MINUTES
time value (1-30). The display flashes the
entered setting.
ƒ
2. Press
and the display shows the new set-
ting.
Touchpad Options-Partition 1 (Default=on)
¾
To change the Fire Panic setting:
1. With the display showing
(current setting), press
ON
The display flashes the entered setting.
ƒ
2. Press
and the display shows the new set-
ting.
Programming the Panel
ENTRY DELAY nnn
EXIT DELAY nnn
EXTENDED DELAY
SIREN TIMEOUT nn
.
PARTITION 1
FIRE PANIC OFF/
1
2
(off) or
(on).