Design Guide | iC7-Automation Air-cooled Enclosed Drives
Table 41: Motor Cable Size Recommendations, 380–500 V
Model
Frame
code
iC7-60EA3A
AE11 +
05-658A
IE11
iC7-60EA3A
05-730A
iC7-60EA3A
05-820A
iC7-60EA3A
05-880A
iC7-60EA3A
2 x AE10 +
05-1000
2 x IE10
iC7-60EA3A
05-1100
iC7-60EA3A
2 x AE11 +
05-1260
2 x IE11
iC7-60EA3A
05-1450
iC7-60EA3A
05-1710
1) With the vertical PE busbar extension installed: 20 x Ø6.5 mm or 16 x Ø6.5 mm + 4 x Ø10.5 mm
2) If the option Top-entry +KDOT is used, the bolt size is M13.
3) If the option Top-entry +KDOT is used, the maximum cable size is 240 mm
4) If the option Top-entry +KDOT is used, the maximum number of motor cables is 4.
112
| Danfoss Drives Oy © 2024.09
(continued)
I
[A]
2
Cable [mm
]
N
672
Cu 2 x (3x185+95)
Al 3 x (3x150+70
Cu)
746
Cu 3 x (3x150+70)
Al 4 x (3x120+41
Cu)
838
Cu 3 x (3x150+70)
Al 4 x (3x150+70
Cu)
899
Cu 4 x (3x120+70)
Al 4 x (3x150+70
Cu)
1021
Cu 4 x (3x150+70)
6 x (3x95+29 Cu)
1123
Cu 4 x (3x185+95)
Al 6 x (3x120+41
Cu)
1287
Cu 6 x (3x120+70)
Al 6 x (3x150+70
Cu)
1481
Cu 6 x (3x150+70)
Al 6 x (3x185+57
Cu)
1746
Cu 6 x (3x185+95)
Al 8 x (3x150+70
Cu)
2
.
Maximum
Maximum
cable size
number
of motor
2
(1)
[mm
]
cables
240 Cu/Al
4
240 Cu/Al
4
240 Cu/Al
4
240 Cu/Al
4
240 Cu/Al
8
240 Cu/Al
8
240 Cu/Al
8
240 Cu/Al
8
240 Cu/Al
8
Number of
(2)
Bolt size
grounding
holes on PE
busbar
M10
4
M10
4
M10
4
M10
4
M10
8
M10
8
M10
8
M10
8
M10
8
AJ389643274589en-000101 / 172F6409A
Specifications
Hole size
of the
grounding
terminal
[mm]
Ø10.5
Ø10.5
Ø10.5
Ø10.5
Ø10.5
Ø10.5
Ø10.5
Ø10.5
Ø10.5
Need help?
Do you have a question about the iC7-Automation and is the answer not in the manual?
Questions and answers