Download Print this page

Motor Cable Size Recommendations, 380-500 - Danfoss iC7-Automation Design Manual

Air-cooled enclosed drives
Hide thumbs Also See for iC7-Automation:

Advertisement

Design Guide | iC7-Automation Air-cooled Enclosed Drives
3) Use bimetallic lugs. No direct aluminum contact to the mains terminals.
4) If the option Top-entry +KCIT is used, the maximum number of mains cables is 4.
5) If the option Top-entry +KCIT is used, the hole size is 13 mm.
Motor Cable Size Recommendations, 380–500 V
9.5.3
Table 41: Motor Cable Size Recommendations, 380–500 V
Model
Frame
code
iC7-60EA3N
FE9
05-206A
iC7-60EA3N
05-245A
iC7-60EA3N
05-302A
iC7-60EA3N
05-385A
iC7-60EA3N
FE10
05-480A
iC7-60EA3N
05-588A
iC7-60EA3A
AE10 +
05-385A
IE10
iC7-60EA3A
05-480A
iC7-60EA3A
05-590A
Danfoss Drives Oy © 2024.09
I
[A]
2
Cable [mm
]
N
206
Cu 1 x (3x70+35)
Al 1 x (3x120+41
Cu)
245
Cu 1 x (3x95+50)
Al 1 x (3x150+41
Cu)
302
Cu 1 x (3x120+70)
Al 2 x (3x95+29 Cu)
385
Cu 2 x (3x95+50)
Al 2 x (3x120+41
Cu)
480
Cu 2 x (3x120+70)
Al 2 x (2x185+57
Cu)
588
Cu 2 x (3x150+70)
Al 2 x (3x240+41
Cu)
394
Cu 1 x (3x185+95)
Al 2 x (3x120+41
Cu)
490
Cu 2 x (3x120+70)
Al 2 x (3x150+70
Cu)
601
Cu 2 x (3x150+70)
Al 2 x (3x185+57
Cu)
Maximum
Maximum
cable size
number
of motor
2
(1)
[mm
]
cables
(3)
(4)
95 Cu/Al
2
(3)
(4)
95 Cu/Al
2
(3)
(4)
95 Cu/Al
2
(3)
(4)
95 Cu/Al
2
(4)
150 Cu/120
3
(3)
Al
(4)
150 Cu/120
3
(3)
Al
(3)
(4)
240 Cu/Al
4
(3)
(4)
240 Cu/Al
4
(3)
(4)
240 Cu/Al
4
Number of
(2)
Bolt size
grounding
holes on PE
busbar
M10
2
M10
2
M10
2
M10
2
M10
4
M10
4
M10
4
M10
4
M10
4
AJ389643274589en-000101 / 172F6409A |
Specifications
Hole size
of the
grounding
terminal
[mm]
Ø10.5
Ø10.5
Ø10.5
Ø10.5
Ø10.5
Ø10.5
Ø10.5
Ø10.5
Ø10.5
111