Design Guide | iC2-Micro Frequency Converters
Table 44: Drive Storage Duration and Reforming Recommendations
Storage duration
Under 2 years
2–3 years
Over 3 years
A
100
75
50
25
0.5
Figure 32: Reforming Procedure for DC Capacitors
A
Reforming voltage (percentage of rated voltage)
Table 45: DC Bus Voltage Ramp-up Value
AC input voltage
1x100–120 V AC
1x200–240 V AC
3x200–240 V AC
3x380–480 V AC
6.4.2

Safe Transportation and Storage

Follow all information on transportation, storage, and proper handling given in the product-specific documentation. That includes:
If the drive is stored before installing it, make sure that the ambient conditions agree to the specifications given in
l
Conditions during
Storage.
If the package is kept in storage for more than 4 months, keep it in controlled conditions:
l
Make sure that the temperature variation is small.
¢
Make sure that the humidity is less than 50%.
¢
Danfoss A/S © 2024.08
Reforming guideline
No reforming required. Connect to mains voltage.
Connect to mains voltage and wait a minimum of 30 minutes before loading the drive.
Using a DC supply connected directly to the DC-link terminals of the drive, ramp up the voltage 0–
100% of DC-bus voltage in increments of 25%, 50%, 75%, and 100% rated voltage under no load for
30 minutes at each increment. See
1
1.5
2
[h]
Mechanical Installation Considerations
Figure
32.
B
B
Hours
Voltage across the DC link
320 V DC
320 V DC
320 V DC
650 V DC
AJ402315027937en-000401 / 130R1239 |
4.2.7.2 Ambient
63

Advertisement

loading
Need help?

Need help?

Do you have a question about the iC2-Micro Series and is the answer not in the manual?

Questions and answers