Programming Guide | VLT® Aqua Drive FC 202
Option
Name
[24]
Analog Input X42/3
[25]
Analog Input X42/5
[29]
Analog Input X48/2
[30]
Ext. closed loop 1
[31]
Ext. closed loop 2
[32]
Ext. closed loop 3
[35]
Digital input select
[37]
Analog Input X49/1
[38]
Analog Input X49/3
[39]
Analog Input X49/5
[133]
Fieldbus REF 1
3-19 Jog Speed [RPM]
Default value:
Size related
Setup:
All setups
Data type:
Uint16
Enter a value for the jog speed n
maximum limit is defined in parameter 4-13 Motor Speed High Limit [RPM]. See also parameter 3-80 Jog/Homing Ramp Time.
3-4* Ramp 1
5.5.3
Configure the ramp times for each of the 2 ramps (parameter group 3-4* Ramp 1 and parameter group 3-5* Ramp 2).
RPM
P 4-13
High-limit
Reference
P 1-25
Motor
speed
P 4-11
Low limit
P 3-*1
Ramp (X)Up
Time (Acc)
t
acc
Figure 49: Ramp 1
130
| © 2024.06
, which is a fixed output speed. The drive runs at this speed when the jog function is activated. The
JOG
Time
P 3-*2
Ramp (X)
Down
Time (Dec)
t
dec
Description
The drive selects AI53 or AI54 as the reference source based on
the input signal defined in option [42] Ref source bit 0 as 1 of the
digital inputs. For more information, see parameter group 5-1*
Digital inputs, [42] Ref source bit 0.
Parameter type:
Conversion index:
Change during operation:
Parameter Descriptions
Range, 0 - par. 4-13 RPM
67
True
AU361182657213en-002101 / 130R0338