Threshold Generation - Danfoss VLT Aqua Drive FC 202 Programming Manual

Hide thumbs Also See for VLT Aqua Drive FC 202:
Table of Contents

Advertisement

Programming Guide | VLT® Aqua Drive FC 202
Table 71: Options
Parameter ID
45-39.0
45-39.1
45-39.2
45-39.3
45-40 Extend Factor
Default value:
1.00f
Setup:
2 setups
Data type:
Uint16
In this parameter, consider the extended factor required for setting the extended threshold generation via parameter 45-45 Threshold
Generation

45-4* Threshold Generation

5.35.5
The parameters in this parameter group support the generation of the CBM thresholds.
45-45 Threshold Generation
Default value:
[0] Off
Setup:
All setups
Data type:
Uint8
Option
Name
[0]*
Off
[1]
Generate now
[2]
Auto generate
[3]
Generate now - previous
[4]
Gen. now - stator
[5]
Gen. now - load
[6]
Gen. now - sensor 1
[7]
Gen. now - sensor 2
© 2024.06
Description
Stator Winding
Load Envelope
Sensor 1 Vibration
Sensor 2 Vibration
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Description
Not applicable.
Based on the selections, threshold for all functions is generated
from actual baseline data.
Not applicable.
Based on the selections, threshold for all functions is generated
from previous baseline data.
Based on the selections, threshold for stator is generated from
actual baseline data.
Based on the selections, threshold for load is generated from
actual baseline data.
Based on the selections, threshold for sensor 1 is generated from
actual baseline data.
Based on the selections, threshold for sensor 2 is generated from
actual baseline data.
AU361182657213en-002101 / 130R0338 |
Parameter Descriptions
Range, 0.05 - 5.00f, Array [6]
-2
True
Option
True
689