Programming Guide | VLT® Aqua Drive FC 202
Option
Name
[61]
Below reference, low
[62]
Above ref, high
[65]
Torque limit
[66]
Current limit
[67]
Out of current range
[68]
Below I low
[69]
Above I high
[70]
Out of speed range
[71]
Below speed low
[72]
Above speed high
[75]
Out of feedack range
[76]
Below feedback low
[77]
Above feedback high
[80]
Thermal warning
[82]
Mains out of range
[85]
Warning
[86]
Alarm (trip)
[87]
Alarm (trip lock)
[90]
Bus OK
[91]
Torque limit and stop
[92]
Brake fault (IGBT)
[94]
Safe stop active
302
| © 2024.06
Description
The motor runs at a reference which is less than the value in
parameter 4-54 Warning Reference Low.
The motor runs at a reference which exceeds the value in
parameter 4-55 Warning Reference High.
The torque exceeds the value in parameter 4-16 Torque Limit
Motor Mode or parameter 4-17 Torque Limit Generator Mode.
The motor current exceeds the value in parameter 4-18 Current
Limit.
The motor current is outside the range set in parameter 4-18
Current Limit.
The motor current is lower than the value in parameter 4-50
Warning Current Low.
The motor current is higher than the value in parameter 4-51
Warning Current High.
The speed is outside the range set in parameter 4-52 Warning
Speed Low and parameter 4-53 Warning Speed High.
The output speed is lower than the value in parameter 4-52
Warning Speed Low.
The output speed is higher than the value in parameter 4-53
Warning Speed High.
The feedback is outside the range set in parameter 4-56 Warning
Feedback Low and parameter 4-57 Warning Feedback High.
The feedback is lower than the limit set in parameter 4-56
Warning Feedback Low.
The feedback exceeds the limit set in parameter 4-57 Warning
Feedback High.
This operand becomes true when the drive detects any thermal
warning, for instance when the temperature exceeds the limit in
the motor, the drive, the brake resistor, or thermistor.
The mains voltage is outside the specified voltage range.
If a warning is triggered, this operand gets the warning number.
A trip alarm is active.
A trip lock alarm is active.
Active communication (no timeout) via the serial communication
port.
If the drive has received a stop signal and is at the torque limit,
the signal is logic 0.
The brake IGBT is short-circuited.
Parameter Descriptions
AU361182657213en-002101 / 130R0338