Danfoss VLT Aqua Drive FC 202 Programming Manual page 206

Hide thumbs Also See for VLT Aqua Drive FC 202:
Table of Contents

Advertisement

Programming Guide | VLT® Aqua Drive FC 202
Option
Name
[107]
Speed 0–HighLim
[108]
Torque ±160%
[109]
Out frq 0–f
[113]
Ext. closed loop 1
[114]
Ext. closed loop 2
[115]
Ext. closed loop 3
[116]
Cascade reference
[117]
Shaft power
[118]
Shaft power 4–20 mA
[130]
Out frq 0–100 4–20mA
[131]
Reference 4–20mA
[132]
Feedback 4–20mA
[133]
Motor cur. 4–20mA
[134]
Torq.0–lim 4–20mA
[135]
Torq.0–nom 4–20mA
[136]
Power 4–20mA
[137]
Speed 4–20mA
[138]
Torque 4–20mA
[139]
Bus ctrl
[140]
Bus ctrl 4–20mA
[141]
Bus ctrl t.o.
[142]
Bus ctrl t.o. 4–20mA
[143]
Ext. CL 1 4–20mA
[144]
Ext. CL 2 4–20mA
[145]
Ext. CL 3 4–20mA
[146]
Cascade ref. 4–20mA
[147]
Main act val
[148]
Main act val 4–20mA
[150]
Out frq 0–F
[156]
Flow rate
206
| © 2024.06
max
4–20mA
max
Description
0–Speed high limit (parameter 4-13 Motor Speed High Limit
[RPM] and parameter 4-14 Motor Speed High Limit [Hz], 0—
20 mA.
0–20 mA.
0–100% (0–20 mA).
0–100% (0–20 mA).
0–100% (0–20 mA).
0–100 Hz.
Minimum reference–maximum reference.
-200% to 200% of parameter 3-03 Maximum Reference.
0–Inverter maximum current (parameter 16-37 Inv. Max.
Current).
0–Torque limit (parameter 4-16 Torque Limit Motor Mode).
0–Motor rated torque.
0–Motor rated power.
0–Speed high limit (parameter 4-13 Motor Speed High Limit
[RPM] and parameter 4-14 Motor Speed High Limit (Hz).
0–100% (0–20 mA)
0–100%
0–100% (0–20 mA)
0–100%
0–100%
0–100%
0–100%
Parameter Descriptions
AU361182657213en-002101 / 130R0338

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT Aqua Drive FC 202 and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents