Programming Guide | VLT® Aqua Drive FC 202
Table 29: Digital Inputs, Function Descriptions - 4
Option
[136]
Pump 7 interlock
[137]
Pump 8 interlock
[138]
Pump 9 interlock
[139]
Pump 1 inverse interlock
[140]
Pump 2 inverse interlock
[141]
Pump 3 inverse interlock
[142]
Pump 4 inverse interlock
[143]
Pump 5 inverse interlock
[144]
Pump 6 inverse interlock
[145]
Pump 7 inverse interlock
[146]
Pump 8 inverse interlock
[147]
Pump 9 inverse interlock
[190]
Emcy mode ref bit 0
[191]
Emcy mode ref bit 1
[192]
Emcy mode ref bit 2
[193]
Emergency mode setup bit 0
[194]
Emergency mode setup bit 1
[195]
Test emcy mode
[196]
Reset emcy mode
154
| © 2024.06
(continued)
Function
See explanation in [130] Pump1 interlock.
See explanation in [130] Pump1 interlock.
See explanation in [130] Pump1 interlock.
Enables a choice between 1 of the 8 preset references according
to
Table
Enables a choice between 1 of the 8 preset references according
to
Table
Enables a choice between 1 of the 8 preset references according
to
Table
Switch between emergency mode setup 1 to 4 in parameter
group 24-0* Emergency Modeand parameter group 24-4* Emer-
gency Mode 2 without changing starting setup mode for the rest
of the parameters.
Switch between emergency mode setup 1 to 4 in parameter
group 24-0* Emergency Modeand parameter group 24-4* Emer-
gency Mode 2 without changing starting setup mode for the rest
of the parameters.
Activation of emergency mode via parameter 24-09 Emergency
Mode Alarm Handling, option [2] Trip all alarms/test with stop
on all alarms and in normal operation mode. The test timer is
set in parameter 24-42 Timeout for Emergency Mode Test, and
countdown starts when the test signal is active.
When operating in emergency mode with impulse signals
(parameter 24-43 Emergency Mode Signal Operation, option [2]
Impulse, set-reset), the reset signal stops the emergency mode
operation.