Sequence Control Instructions
Differences between
Interlocks and Jumps
Item
Instruction execution
Output status in instructions
Bits in OUT, OUT NOT,
OUTB(534)
Status of timer instructions
(except (TTIM(087),
TTIMX(555), MTIM(543), and
MTIMX(554))
3-5-4

INTERLOCK and INTERLOCK CLEAR: IL(002) and ILC(003)

Purpose
Ladder Symbols
Variations
Applicable Program Areas
Description
210
The following table shows the differences between interlocks (created with
IL(002)/ILC(003), MILH(517)/MILC(519), or MILR(518)/MILC(519)) and jumps
created with JMP(004)/JME(005).
Treatment in IL(002)/ILC(003), MILH(517)/
MILC(519), or MILR(518)/MILC(519))
Instructions other than OUT, OUT NOT,
OUTB(534), and timer instructions are not
executed.
Except for outputs in OUT, OUT NOT,
OUTB(534), and timer instructions, all out-
puts retain their previous status.
OFF
Reset
Interlocks all outputs between IL(002) and ILC(003) when the execution con-
dition for IL(002) is OFF. IL(002) and ILC(003) are normally used in pairs.
IL(002)
ILC(003)
Variations Interlocks when OFF/Does Not interlock when ON IL(002)
Immediate Refreshing Specification
Variations
Executed Each Cycle for ON Condition
Immediate Refreshing Specification
Block program areas
Not allowed
When the execution condition for IL(002) is OFF, the outputs for all instruc-
tions between IL(002) and ILC(003) are interlocked. When the execution con-
dition for IL(002) is ON, the instructions between IL(002) and ILC(003) are
executed normally.
Execution
condition
Interlocked section
of the program
No instructions are executed.
All outputs retain their previous status.
All outputs retain their previous status.
Operating timers (TIM, TIMX(550),
TIMH(015), TIMHX(551), TMHH(540),
TMHHX(552), TIMU(541), TIMUX(556),
TMUH(544), TMUHX(557) only) continue
timing because the PVs are updated even
when the timer instruction is not being exe-
cuted.
Step program areas
Subroutines
Not allowed
OK
Execution
Execution
condition ON
condition OFF
Normal
execution
Section 3-5
Treatment in
JMP(004)/JME(005)
Not supported
ILC(003)
Not supported
Interrupt tasks
OK
Outputs
interlocked.