Simple Data Setting

Potentiometer setting (Refer to 5. OPERATING THE INVERTER) and
digital setting are both available for simple accel/decel operation of the VS
mini.
Frequency reference by potentiometer signal is set with initial setting
(n03=0).
Factory setting of the model with operator (without potentiometer) is set by
digital operator (n03=1).
Following is an example in which the function LEDs are used to set
frequency reference, acceleration time, deceleration time, and motor
direction.
Operation Steps
1. Turn ON the power supply.
2. Set constant n03 to 1.
3. Set the following constants.
n16 : 15.0 (acceleration time)
n17 : 5.0 (deceleration time)
4. Select forward or reverse run by
NOTE
pressing q or w key.
Examine the application.
(Never select REV when
reverse run is prohibited.)
5. Set the reference by pressing q or w
key.
RUN
6. Press
.
7. Press
to stop.
STOP
Status indicator lamp
Operator
Display
0.0
1
15.0
5.0
(Forward)
or
(Reverse)
60.0
0.0 to 60.0
60.0 to 0.0
: BLINKING (Long Blinking)
LED
Status Indicator
Display
LED
RUN ALARM
FREF
RUN ALARM
PRGM
RUN ALARM
PRGM
RUN ALARM
F/R
RUN ALARM
FREF
RUN ALARM
FOUT
RUN ALARM
FOUT
: BLINKING
: OFF
35