Advertisement

03.99
4.3

Initial process and initial data setting

Initial process
Error status and
error handling
Initial data setting
NOTE
NOTE
Siemens AG
6SE7087-6NX84-0GB0
SIMOVERT MASTERDRIVES
Initial process is used by CBL to show the user a power-up of the
converter or a re-initializing of CBL. The user has to acknowledge this
request with the complete flag.
Initial process
request
Initial process
complete
Error status
Error reset
request
Ready
Fig. 4-2
Initial process sequence (incl. error handling)
If an error occurs in the converter the status bit error status (RX(n+1)A
is activated. Bit Remote Ready (RX(n+1)B goes inactive. By activating
control bit error reset request (RY(n+1)A you can reset the error
status. This bit is edge sensitive! A 0-1-transition clears the error status.
If the fault in the converter is still active, the error status can't be
cleared!
Initial data setting is used by the PLC program to reset the CBL
interface to CC-Link. Setpoints (written to converter by frequency set
command) will be cleared also with this sequence.
Initial data
setting request
Initial data
setting complete
Ready
Fig. 4-3
Initial data setting sequence
With Initial data setting you can't reset the converter. You only clear
the CC-Link interface!
If drive is controlled with fixed setpoints and the control bits STF or STR
and RL, RM or RH are still be set after Iniital data setting, drive will
start immediately! Using Initial data setting sequence these important
control bits has to be cleared by the user!
Operating Instructions
Communication via CC-Link
RX(n+1)8
RY(n+1)8
RX(n+1)A
RY(n+1)A
RX(n+1)B
RY(n+1)9
RX(n+1)9
RX(n+1)B
4-5