Commissioning

Check the existing
board combinations
(dependent on the
particular
configuration)
Commissioning
steps
Siemens AG
6SE7087-6CX84-3DD0
SIMOVERT MASTERDRIVES
♦ CU1 and TSY (only with RIF)
♦ CU2 / CUVC (RIF or RIF2)
♦ T300 (RIF or RIF2)
♦ Define the power supply source:
• to adjust S1 refer to Table 4-1 (only RIF)
♦ Define the resolver type (field voltage, field frequency, ratio)
♦ Adjust the field voltage using S2, so that the resolver position
signals do not exceed 2.2 V
• V
<= ü
field(max)
• to adjust S2, refer to Table 4-2
• adjust the field frequency using S3 (refer to Table 4-3)
♦ X401:
RIF:
RIF: Connect-up the resolver,
RIF2:
Connect-up the resolver with DSUB-9
♦ X402:
Alternative for RIF2: Connect-up the resolver with
♦ X403:
Connect-up CU2 / CUVC or TSY (only RIF) or T300
♦ X404:
If required connect-up the external power supply (only
RIF).
♦ Check the shield and grounding of the board at both ends.
♦ Parameterizing the control board:
• CU2:
Set parameter P208 to "digital tachometer" (P208 = 1).
Enter the pulse number in parameter P209 (Table 4-4)
• CUVC:
Set parameter P130 to "pulse encoder" (P130 = 11).
Enter the pulse number in parameter P151 (Table 4-4)
S1 (only RIF)
Define the RIF board power supply
Setting 1
Supplied via X403 through CU2 / CUVC / TSY / T300
Setting 2
Supply via X404 from an external 24 V power supply
Table 4-1
Resolver-Interface
:
RMS
. 2.2 V
res
DSUB-26
Commissioning
4-1