Commissioning
7.4.

Configuration of further parameters

Information
7.4.1.

Speed setting

28
3.
Turn inside shaft [2] using an appropriate screwdriver until the black strip [3] is
at the same position as the red label [1].
4.
Operate actuator to end position OPEN.
5.
Stick the green label [3] onto the black strip [3] and make sure that they com-
pletely overlap.
Either the AUMA Assistant App or AUMA CDT software is required to use the
complete range of configuration options.
The user level defines which parameters are displayed or can be changed.
For further information relating to user levels and passwords, please refer to
33, Table
12.
The speeds are determined by the motor speed. The motor speed and thus the
actuator speed can be modified using the AUMA Assistant App or AUMA CDT.
Setting is made via a percentage within the range of 10 % to 100 %, whereby 100
% corresponds to the maximum actuator speed.
The speeds can be individually set for the following functions:
Standard speed for operations in directions OPEN and CLOSE and back
(parameter: Motor speed 1).
Alternative standard speed if different speeds are required for operation in dir-
ections OPEN and CLOSE or if continuous changes between two specified are
required (parameter: Motor speed 2).