Upgrade kit instructions
00825-0200-3810
Emerson.com
Figure 2-16: Install Wiring Terminal Block Connectors to the CPU Module
A. Conduit wiring entry (four entries)
B. Pulse out
C. Ground/Prover switch -
D. Prover switch +
E. Temperature transmitter +
F. Temperature transmitter -
G. Pressure transmitter +
H. Pressure transmitter -
I. Internal ground lug
J. Ethernet (orange and white wire)
K. Ethernet (orange wire)
L. Ethernet (green and white wire)
M. Ethernet (green wire)
N. 24 VDC loop power
O. 10.4 - 36 VDC power
P. Fuse holder
All of the terminations in the 3810 Series electronics are removable terminal
blocks. Removing the terminal blocks from the modules before terminating wires
to them makes wiring easier.
document also includes wiring tables and illustrations for each of the connectors
3810 Communication and Output settings
Install
February 2024
of this
27