Instruction Manual
D450396T012
March 2024
RJ600 Series Instruction Manual
WARNING
Failure to follow these instructions or
to properly install and maintain this
equipment could result in an explosion
and/or fire causing property damage and
personal injury or death.
Fisher™ equipment must be installed,
operated and maintained in accordance
with federal, state and local codes,
rules and regulations and Emerson
Process Management Regulator
Technologies, Inc. The installation in
most states must also comply with
NFPA No. 54 and 58 standards.
Only personnel trained in the proper
procedures, codes, standards
and regulations of the LP-Gas
industry should install and service
this equipment.
Things to tell the gas customer
1. Show the customer the vent or vent assembly or
vent tube. Stress that this opening must remain
unobstructed at all times. Tell the customer to
check the vent opening after a freezing rain, sleet
storm or snow to make sure ice has not formed in
the vent.
2. Show the customer the shutoff valve on the
container. The customer should close this valve
immediately if gas is smelled, appliance pilot lights
fail to stay on or appear higher than usual or any
other abnormal situation occurs.
3. Tell the customer to call your company to service
the regulator if the regulator vents gas or a
leak develops in the system. Only a qualified
gas service person should install or service
the regulator.
TYPE RJ622
TYPE RJ652
Figure 1. Types RJ622, RJ642 and RJ652 Regulators
4. Tell the customer to call your company to have a
leak check performed if the gas supply has been
shutoff or interrupted for any reason. A leak check
must be performed by a qualified gas service
person on the piping system immediately after
turning on the gas supply.
Introduction
Scope of the Manual
This Instruction Manual covers Installation and
Maintenance for the RJ600 Series regulators, which
includes second stage and two psig service regulators
used on LP-Gas vapor service applications. They are
not to be used on liquid service. These regulators
are intended for jurisdictional applications where the
pressure coming from the first stage is higher than
10 psig / 0.7 bar.
RJ600 Series
TYPE RJ642

Advertisement

Table of Contents
loading

Summary of Contents for Emerson FISHER RJ600 Series

  • Page 1 Fisher™ equipment must be installed, operated and maintained in accordance TYPE RJ622 with federal, state and local codes, rules and regulations and Emerson Process Management Regulator Technologies, Inc. The installation in most states must also comply with NFPA No. 54 and 58 standards.
  • Page 2: Specifications

    RJ600 Series Specifications Specifications section, Tables 1 and 2 list the specifications for these regulators. Contact the factory if the regulator is to be used on any service other than LP-Gas, natural gas or air. The following information is located on the spring case: Type number, orifice size, spring range and date of manufacture.
  • Page 3: General Installation Instructions

    RJ600 Series 3 ft / 0.91 m VENT POINTED DOWN T14446-A2 Figure 2. Regulator with Vent Pointed Down Table 1. Relief Valve Specifications MAXIMUM INLET PRESSURE TO NOT EXCEED NOMINAL RELIEF VALVE OUTLET PRESSURE WITH DISC REMOVED TYPICAL SETPOINT START-TO-DISCHARGE TYPE Inlet Pressure Maximum Outlet Pressure...
  • Page 4 RJ600 Series Table 2. Capacity and Connection Sizes INLET PRESSURE AT CAPACITY, REGULATOR TYPE INLET OUTLET OUTLET RATED CAPACITY BTU/HR APPLICATION NUMBER CONNECTION CONNECTION PRESSURE SETTING PROPANE psig 875,000 0.69 1,450,000 1/2 in. FNPT / RJ622-BCF DN 15 1,550,000 1,700,000 1/2 in.
  • Page 5: Indoor Installations

    RJ600 Series TO APPLIANCE VENT ASSEMBLY VENT LINE VENT OPENING MUST BE AT LEAST 3 ft / 0.91 m HORIZONTALLY FROM ANY BUILDING OPENING BELOW IT BASEMENT FROM FIRST STAGE REGULATOR T14445-A2 Figure 3. Basement Installation Regulators Subjected to Heavy or heavy snows.
  • Page 6: Overpressure Protection

    RJ600 Series Outdoor Installations with Underground If any portion of the regulator is exposed to an overpressure condition that Vent Lines exceeds the limits in the Specifications When installed per code, the underground vent line section, it must be inspected for damage must not restrict the gas flow from the regulator’s that may have occurred.
  • Page 7 RJ600 Series service conditions or the requirements the condition of the relief valve spring, main spring of local, state and federal regulations. and internal spring barrel area. A more detailed Even under ideal conditions, these examination will require shutting down of the gas regulators should be replaced after system and the complete removal of the adjusting 20 years from date of manufacture...
  • Page 8 Technologies, Inc. All rights reserved. 03/24. Emerson The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher™ is a mark owned by Fisher Controls International LLC, a...