Restore Application - Nailor 35SW Manual

Fan powered terminal unit with epic ecm motor
Table of Contents

Advertisement

Procedure to set the advanced options (continue)
PROCEDURE
8 Set the temperature sensor
calibration constant.
9 Select a new configuration
function or exit.
Restore Application
Choose the RSTR function to reset the EZvav controller to the original configuration and settings. Use it also to change the units of
measure to display on a EZvav sensor. There are two versions of the application program in the controller.
• The Metric version displays temperature in Celsius and uses metric values for units of measure.
• The English version displays temperature in Fahrenheit and uses English values for units of measure.
Access to the Restore Application function requires entering Password 2 which is described in the topic Getting started with
configuration on page 14.
Tip:
Once the following procedure is started, all steps must be completed in order.
CAUTION Choosing RSTR deletes all previously
configured values including balancing values and
passwords. Only the BACnet communications
settings will remain unchanged.
Procedure to restore application
PROCEDURE
1 Starting display
Date: 10-2016
Supersedes: 7-2016
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Installation and Operation Manual
1. Press the
or
constant. The set point will change in 0.1 minute
increments.
• For a low input reading enter a positive correction
value.
• For a high input reading enter a negative correction
value.
2. Press the
button to save the set point and
advance to the next function.
1. Press the
or
following:
• STPT, FLOW, BOX, or RSTR options
• BACK to choose .another configuration function
• EXIT to return to the temperature display.
2. Press the
button to select the next function.
1. Start at the temperature display.
2. Press the
and
• If Password 2 is not required, the display changes to
CNFG.
• If required, enter Password 2. The display changes to
CNFG when Password 2 is correct.
Page 23 of 48
EZvav Digital Controls
STEPS
buttons to set the calibration
buttons to select one of the
STEPS
buttons together.
STE DISPLAY
OO
CALIB
ADVC
STE DISPLAY

3
237
////
IOM-EZVAVINST

Advertisement