Nailor 35SW Manual page 9

Fan powered terminal unit with epic ecm motor
Table of Contents

Advertisement

DESCRIPTION:
• 18 ga. (1.31) galvanized steel
channel frame with 20 ga. (1.00)
casing components.
• 16 ga. (1.61) galvanized steel
inclined opposed blade dampers.
45° rotation. RH CW to close. LH
CCW to close.
• Separate outside ventilation air
inlet.
• Ultra-high efficiency ECM
fan motor. EPIC fan volume
controller.
• Multi-point averaging Diamond
Flow sensor. Supplied with
balancing tees.
• Universal access panels on all
4 sides.
• 3/4"
(19)
dual
density
insulation, coated to prevent
air erosion, meets requirements
of NFPA 90A and UL 181.
• Single point electrical and/or
pneumatic main air connection.
• Discharge opening for flanged
duct connection.
• Full
enclosure
for
factory
mounted
DDC
and
analog
electronic controls.
• Choice of right or left-hand
primary inlet location. Hand of
unit is determined by location of
primary inlet looking in direction
of airflow. Right-hand illustrated.
OPTIONS:
Digital Controls:
q
Factory mounted
(supplied by others)
q
Field mounted
(supplied by others)
Liner:
q
Fiber-free
q
Steri-liner
q
Steri-liner + Perforated metal
q
Perforated metal
q
Solid metal
q
1" (25) fiberglass
Other:
q
Left-hand controls location
q
Left-hand primary inlet location
q
Toggle disconnect switch
q
Fan unit fusing
q
24/24V Isolation transformer
q
Cross Flow Sensor (not on
primary inlet)
q
'Q' Option – Induced
Air Inlet Attenuator. (not
available w/FN2 option).
q
Top entry induced air inlet
q
1" (25) Throwaway filter
q
2" (51) MERV 8 filter
q
Hanger brackets.
q
1/4-turn fasteners (access
panel)
q
FN2 90° Line Voltage
Enclosure
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
FAN POWERED TERMINAL UNIT WITH
OUTSIDE AIR INLET • EPIC ECM MOTOR
SERIES FLOW • CONSTANT OR VARIABLE VOLUME
MODELS: 35S-OAI, 35SW-OAI AND 35SE-OAI
UNIT SIZES 2 – 6
Model 35S-OAI • Basic Unit
12"
MULTI-POINT
(305)
FLOW
10"
SENSOR
(254)
OUTSIDE
AIR INLET
DIA. =
NOM. –
1/8" (3)
W3
PH
+
W3
11 1/2"
(292)
PW
5 3/4"
PRIMARY
(146)
AIR INLET
A =
5 1/2"
(140)
RIGHT-HAND
PRIMARY AIR
VALVE CONTROL
ENCLOSURE
Dimensional Data
Unit
Inlet
Outside
Size
Size
Inlet Size
6, 8
4, 5, 6
2
(152, 203)
(102, 127, 152)
6, 8, 10
4, 5, 6
3
(152, 203, 254)
(102, 127, 152)
8, 10, 12**
6, 7, 8
4
(203, 254, 305)
(152, 178, 203)
10, 12**, 14**
6, 7, 8
5
(254, 305, 356)
(152, 178, 203)
10, 12**, 14**
6, 7, 8
6
(254, 305, 356)
(152, 178, 203)
Primary/Inlet Dimensions
Size
W1 or W2
4, 5, 6
12 (305)
Oval Inlet Dimensions
7, 8
14 (356)
10
16 (406)
Size
12** 12 13/16 x 9 13/16 (325 x 249)
12**
19 (483)
14** 16 1/16 x 9 13/16 (408 x 249)
14**
20 (508)
q
FN3 Remote Line Voltage Controls
Enclosure. (See submittal FN3)
q
Dust tight enclosure seal
q
Remote user disconnect
Seismic Certification:
q
Seismic Source International (Standard)
q
HCAI (formerly OSHPD, California)
q
Special Features: _________ .
'Q' OPTION INDUCED
AIR ATTENUATOR
W2
2
L C
W2
W3
2
A
L C
L C
W1
14" (356)
W1 + W2
W3 = W1 + W2
2
HINGED FAN
H -
H
CONTROLS
1" (25)
ENCLOSURE
Induced Air Inlet
W
H
L
B
Side (std.)
IW x IH
18
14
51 1/2
6
8 x 10
(457)
(356)
(1308)
(152)
(203 x 254)
18
18
51 1/2
3 1/2
12 x 14
(457)
(457)
(1308)
(89)
(305 x 356)
26
18
56 1/2
6
14 x 14
(660)
(457)
(1435)
(152)
(356 x 356)
26
18
56 1/2
5
14 x 14
(660)
(457)
(1435)
(127)
(356 x 356)
30
19
59 1/2
6
16 x 15
(762)
(483)
(1511)
(152)
(406 x 381)
**
Flat oval inlets
PW x PH
Page 1 of 2. For heat options; see page 2.
DATE
2 - 6 - 23
L
IW + 2" (51)
INDUCED
AIR
FAN
TW
W
1"
(25)
TL
5 3/4"
(146)
OPTIONAL
90° FN2 HINGED
FAN CONTROLS
ENCLOSURE
6 3/4"
(171)
14" (356)
8" (203)
IW
LEFT-HAND
PRIMARY AIR
IH
VALVE CONTROL
ENCLOSURE
Outlet
Top (opt.)
Discharge
Side Inlet
TL x TW
DW x DH
10 x 14
9 1/4 x 10 1/2
10 x 12
(254 x 356)
(235 x 267)
(254 x 305)
14 x 14
9 1/4 x 10 1/2
14 x 16
(356 x 356)
(235 x 267)
(356 x 406)
12 x 22
12 x 10 1/2
16 x 16
(305 x 559)
(305 x 267)
(406 x 406)
12 x 22
13 1/4 x 11 1/2
16 x 16
(305 x 559)
(337 x 292)
(406 x 406)
14 x 26
13 1/4 x 11 1/2
17 x 18
(356 x 660)
(337 x 292)
(432 x 457)
Electrical Data
Unit
EPIC ECM Motor FLA
Size
Motor HP 120V 208V 240V 277V
4.0
2.7
*
2
5.0
3.4
*
3
6.9
4.6
*
4
9.0
6.1
*
5
11.9
7.3
*
6
*
The ECM is a variable horsepower motor. Refer to
Selectworks schedule for actual power consumption.
FLA = Full load amperage. All motors are single
phase/60 Hz.
Listed
Dimensions are in inches (mm).
B SERIES
SUPERSEDES DRAWING NO.
3500
11 - 15 - 22
B
DW
DH
15"
(381)
OPTIONAL
INDUCED AIR
INLET FILTER
Filter Size
Top Inlet
(std.)
(opt.)
14 x 16
(356 x 406)
16 x 16
(406 x 406)
16 x 25
(406 x 635)
16 x 25
(406 x 635)
18 x 28
(457 x 711)
2.6
2.6
3.3
3.3
4.5
4.2
5.8
5.6
7.3
7.2