Figure 8-6 Dual duct sequence
Max heating airflow
Section 9: System Integration and Networking
Topics in this section cover integrating the controllers into a building automation network. These are advanced reference topics
for control technicians and engineers.
The controllers can be installed as standalone controllers or they can be connected to a BACnet MS/TP network. The topics in this
section are reference material for control technicians or engineers who are planning, installing, and setting up controllers that are
connected to a network.
In addition to the information in this section, you will also need the following information.
• Detailed plans and drawings for the building automation system.
• Information about the facility LAN including routers, switches, and network firewalls.
• Sequences of operation for other BACnet devices that will monitor or interact with EZvav controllers.
Integration topics

Connecting to an MS/TP network .....................................................................................................41

Setting up network communications ................................................................................................42
BACnet objects .................................................................................................................................44
Connecting to an MS/TP network
EZvav controllers are BACnet MS/TP compliant controllers. Connect them only to a BACnet MS/TP network.
To enter the BACnet device instance, MAC address, and network baud, see the topic Setting up network communications on page 42
Figure 9-1 MS/TP network wiring and EOL switches
COMM
ON CTS
READY
1
2
AI1
GND
AO3
BACnet MS/TP
AO4
AI5
AI6
GND
AI7
SC
BO5
BO6
BO7
SC
BO8
24VAC
End of line controller
with grounded shield
EOL switches ON
Date: 10-2016
Supersedes: 7-2016
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Installation and Operation Manual
Dual duct
minimum
airflow
MIN
CLG
CFM
HTG SPAN
HTG SP
ON
1
2
COMM
READY
AI1
GND
AO3
AO4
AI5
AI6
GND
AI7
SC
BO5
BO6
BO7
SC
BO8
24VAC
Mid line controller
EOL switches OFF
Page 41 of 48
EZvav Digital Controls
Max. cooling airflow
MIN
HTG
CFM
Room temp increase
CLG SPAN
CLG SP
ON
1
2
ON CTS
1
2
BACnet MS/TP
ON
1
2
COMM
ON CTS
READY
1
2
AI1
GND
AO3
AO4
BACnet MS/TP
AI5
AI6
GND
AI7
SC
BO5
BO6
BO7
SC
BO8
24VAC
End of line controller
with open shield
EOL switches ON
IOM-EZVAVINST